22
EG
No.
Accompanying parts
Q’ty
1
2
2
2
No.
Accompanying parts
Q’ty
2
3
Remote controller
(comes with
20 cm wire)
Machine screws
M4 x 25
Wood screws
Spacers
Clamper
Wire joints
6-2. Basic Wiring Diagram
6-3. Wiring System Diagram for Group Control
This diagram shows when several units (max. 8) are controlled by a remote controller. In this case, the remote controller can be
connected at any indoor unit.
CAUTION
• Make correct wiring
without any mistakes
(incorrect wiring will
damage the equip-
ment).
Standard
remote control
Indoor unit
Indoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Inter-unit
control
wiring
Terminal
3P
Remote
controller
Branch wiring for
group control
: Ground (earth)
Outdoor unit
Outdoor unit
Outdoor unit
Multiple
remote control
RED
WHT
BLK
RED
WHT
BLK
RED
WHT
BLK
Wiring procedure
Do the wiring according to the wiring diagram.
• Recommended wire diameter and allowable lenght for remote
control wiring and its branch wiring:
0.75 mm
2
Max. 500 m
• Diagram of outer dimensions
Wiring procedure
Wire according to the left diagram:
• Set RC address switch S2 of each outdoor unit then turn on
the power.
• Address setting is executed with the remote control or by
pressing A.ADD button (S1) of each outdoor unit.