background image

IST-2137.EC03.01/E

 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag.18/20

 

 

 

 

TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI ) 

Tel. +39 02 26922890 - Fax +39 02 2133734

 

 

 

Tabella 4: Interferenze con altri Gas / Table 3: Typical cross Sensitivities / Tableau 3: Interférence 

GAS / GAZ 

Gas Utilizzato 

Test Gas Used 
Gaz utilisé

 

ppm letti come gas 
Gas concentration equivalent (ppm) 
ppm lu comme gaz 

 

 

SE137EHCN 

(7)

 

SE137EN 

(8)

 

SE137EN2 

(9)

 

SE137EHCL 

(10)

 

SE137ECL 

(11) 

 

(7)

 

Acido cianidrico 

Hydrogen cyanide / Cyanure d'hydrogène

 

10 ppm 

10 

3.5 

 

(10)

 

Acido cloridrico 

Hydrogen cloride / 

Acide chlorhydrique

 

10 ppm 

10 

 

Ammoniaca / 

Ammonia / Ammoniac

 

100 ppm 

 

Acetato di etile / 

Ethyl acetate / Acétate d'éthyle

 

100 ppm 

< 0.5 

 

Biossido di zolfo /

 

Sulphur di

oxide / Dioxyde de soufre

 

20 ppm 

40 ÷ 75 

- 0.4  

< 2 

 

(9)

 

Biossido di azoto 

Nitrogen dioxide / dioxyde d’azote

 

5 ppm 

- 20 ÷ -10 

< 1.5 

< ± 0.2

 

 

(11) Cloro / Clorine / Chlore

 

5 ppm 

≈ 10 

< ± 0.2 

5

 

 

Etanolo / 

Ethanol / Éthanol

 

100 ppm 

< 1 

 

Etilene / 

Ethylene / Éthylène

 

100 ppm 

< 25 

< 1 

 

Idrogeno / 

Hydrogen / Hydrogène

 

1000 ppm 

< 1 

 

(6) Idrogeno Solforato 

Hydrogen sulphide / 

Sulfure d'hydrogène 

15 ppm 

~ 90

 

≈ 1.5 

- 19  

45 

< -15 

 

Monossido di carbonio 

Carbon Monoxide / Monoxyde de carbone

 

300 ppm 

< 15 

< 2 

 

(8) Ossido di azoto / 

Nitric oxide / Oxyde nitrique

 

35 ppm 

-28 ÷ 0 

35 

< 1 

 

Toluene / 

Toluene / Toluène

 

50 ppm 

< 1.5 

 

Tabella 5 / 

Table 5 / Tableau 5

 

SE137EA / SE137EA-H (

Ammoniaca / Ammonia / Ammoniac

)

 

“S1-SET” 

(Dip-Switch)

 

Livelli Allarme (

Relé

Alarm levels(

Relays

) / Niveaux d'alarmes(

Relais

)

 

Ritardo dei Relé (

in Secondi

Relays Delay (

Seconds

) / retarde du relais (

Secondes

)

 

 

ALARM 1 

ALARM 2 

ALARM 3 

ALARM 1 

ALARM 2 

ALARM 3 

FAULT

 

OFF 

OFF 

OFF 

25 ppm 

35 ppm 

50 ppm 

12 

30 

60 

30 

ON 

OFF 

OFF 

25 ppm 

50 ppm 

75 ppm 

12 

30 

60 

30 

OFF 

ON 

OFF 

25 ppm 

50 ppm 

100 ppm 

12 

30 

60 

30 

ON 

ON 

OFF 

50 ppm 

100 ppm 

200 ppm 

12 

30 

60 

30 

OFF 

OFF 

ON

 

TLV-TWA

 

(COSHH)

 

25 ppm 

TLV-STEL

 

(COSHH)

 

35 ppm 

TLV-C 

50 ppm

 

30 

ON

  

OFF 

ON

 

Risevato 

/ Reserved / Réservé

 

Risevato 

/ Reserved / Réservé

 

OFF 

ON

  

ON

 

Risevato 

/ Reserved / Réservé

 

Risevato 

/ Reserved / Réservé

 

ON 

ON 

ON 

Risevato 

/ Reserved / Réservé

 

Risevato 

/ Reserved / Réservé

 

Tabella 6 / 

Table 6 / Tableau 6 

SE137EC-S / SE137EC-H (

Monossido di carbonio / Carbon monoxyde / Dioxyde de carbone

“S1-SET” 

(Dip-Switch)

 

Livelli Allarme (

Relé

Alarm levels(

Relays

) / Niveaux d'alarmes(

Relais

)

 

Ritardo dei Relé (

in Secondi

Relays Delay (

Seconds

) / retarde du relais (

Secondes

)

 

 

ALARM 1 

ALARM 2 

ALARM 3 

ALARM 1 

ALARM 2 

ALARM 3 

FAULT

 

OFF 

OFF 

OFF 

25 ppm 

50 ppm 

100 ppm 

12 

30 

60 

30 

ON 

OFF 

OFF 

50 ppm 

70 ppm 

100 ppm 

12 

30 

60 

30 

OFF 

ON 

OFF 

50 ppm 

100 ppm 

200 ppm 

12 

30 

60 

30 

ON 

ON 

OFF 

Risevato

 

Reserved

 

Réservé

 

12 

30 

60 

30 

OFF 

OFF 

ON

 

TLV-TWA

 

(COSHH)

 

30 ppm 

TLV-STEL

 

(COSHH)

 

200 ppm 

TLV-C 

250 ppm

 

30 

ON

  

OFF 

ON

 

TLV-TWA

 

(OSHA)

 

25 ppm 

TLV-STEL 

50 ppm

 

TLV-C

 

(OSHA)

 

200 ppm

 

30 

OFF 

ON

  

ON

 

Risevato 

/ Reserved / Réservé

 

Risevato 

/ Reserved / Réservé

 

ON 

ON 

ON 

Risevato 

/ Reserved / Réservé

 

Risevato 

/ Reserved / Réservé

 

Tabella 7 / 

Table 7 / Tableau 7

 

SE137ES (

Biossido di zolfo / Sulfur dioxide / Dioxyde de soufre

)

 

“S1-SET” 

(Dip-Switch)

 

Livelli Allarme (

Relé

Alarm levels(

Relays

) / Niveaux d'alarmes(

Relais

)

 

Ritardo dei Relé (

in Secondi

Relays Delay (

Seconds

) / retarde du relais (

Secondes

)

 

 

ALARM 1 

ALARM 2 

ALARM 3 

ALARM 1 

ALARM 2 

ALARM 3 

FAULT

 

OFF 

OFF 

OFF 

1,5 ppm 

2,5 ppm 

5,0 ppm 

12 

30 

60 

30 

ON 

OFF 

OFF 

2,5 ppm 

5,0 ppm 

7,5 ppm 

12 

30 

60 

30 

OFF 

ON 

OFF 

3,0 ppm 

6,0 ppm 

9,0 ppm 

12 

30 

60 

30 

ON 

ON 

OFF 

5,0 ppm 

10,0 ppm 

20,0 ppm 

12 

30 

60 

30 

OFF 

OFF 

ON

 

TLV-TWA

 

(COSHH)

 

2 ppm 

TLV-STEL

 

(COSHH)

 

5 ppm 

TLV-C 

10 ppm

 

30 

ON

  

OFF 

ON

 

Risevato 

/ Reserved / Réservé

 

Risevato 

/ Reserved / Réservé

 

OFF 

ON

  

ON

 

Risevato 

/ Reserved / Réservé

 

Risevato 

/ Reserved / Réservé

 

ON 

ON 

ON 

Risevato 

/ Reserved / Réservé

 

Risevato 

/ Reserved / Réservé

 

Summary of Contents for SE137E Series

Page 1: ...tecniche Technical specifications Caract ristiques techniques 2 IT DESCRIZIONE 4 NOTE SUL GAS RILEVATO DAI VARI MODELLI 4 FUNZIONAMENTO 5 INSTALLAZIONE 6 AVVERTENZE 6 VERIFICHE E CALIBRAZIONE 6 EN DES...

Page 2: ...chelle 500 ppm 500 ppm 1000 ppm 1000 ppm 150 ppm 500 ppm Vita media in aria pulita Average Life in fresh air Vie moyenne en air pur 2 anni years ans 2 anni years ans 3 anni years ans 2 anni years ans...

Page 3: ...onth mois 2 mese month mois 3 mese month mois 2 mese month mois Risoluzione Resolution R solution 0 1 ppm 1 ppm 1 ppm 0 7 ppm 0 1 ppm Tempo di risposta T90 Response Time T90 Temps de r ponse T90 120 s...

Page 4: ...te respirato dalle persone dai polmoni raggiunge il sangue dove impedisce il trasporto dell ossigeno ai tessuti e agli organi SE137EC H identico al precedente ma utilizza un sensore di livello superio...

Page 5: ...stato Il rel ALARM 2 interviene dopo 30 secondi oppure immediatamente quando superato il livello TLV STEL Il 3 Led rosso ALARM 3 si accende se la concentrazione di gas supera il 3 livello d allarme im...

Page 6: ...ento Guasti Importante terminata l installazione alimentare l apparecchio attendere circa 20 30 minuti e poi per adattare il sensore alle condizioni ambientali eseguire se necessario la Regolazione de...

Page 7: ...pegner per conferma SE137EA SE137EA H SE137EC S SE137EC H SE137ES SE137EH SE137EHCN SE137EN SE137EN2 SE137EHCL SE137ECL 4 8 mA 15ppm NH3 4 8 mA 15ppm CO 6 4 mA 3ppm SO2 4 8 mA 5ppm H2S 8 mA 2 5ppm HCN...

Page 8: ...as to air is 0 6 His TWA is 25ppm Time Weighted Average and STEL is 35ppm Short Term Exposure Limit His LEL Lower Explosivity Limit is 15 v v volume This gas is irritating to the eyes and mucous memb...

Page 9: ...mperature compensated but is sensitive to extreme humidity variations The cali bration is carried out with specific gas to be detected Anyway it can contemporaneously detect other gases that should be...

Page 10: ...ered in parallel it is necessary to consider the voltage drop across the supply cable Normally use a two wire cable not shielded for power supply the conductors for output relay If the output signal i...

Page 11: ...levant relays relay FAULT with the yellow Led relay ALARM1 with the 1 red Led relay ALARM2 with the 2 red Led relay ALARM3 with the 3 red Led At the end all the Led will remain lighted for around 5 se...

Page 12: ...1 mA 30 ppm 2 SE137EHCL 10ppm Hydrogen cloride HCL in Nitrogen 0 3 0 5 l min 192 208 mV 19 2 20 8 mA 10 ppm 1 SE137ECL 10ppm Nitrogen dioxide NO2 in air 1 l min 192 208 mV 19 2 20 8 mA 10 0 ppm 0 5 FR...

Page 13: ...les voies respiratoires L inhalation peut causer un oed me pulmonaire mai aussi avoir des effets sur le sang provo quant la formation de m th moglobine Dans les cas plus graves il peuve entra ner la m...

Page 14: ...e Capteur par une nouvelle Le type commander est indiqu en Page 1 La proc dure de substitution est d crite dans la documentation jointe la cartouche Si la led jaune est allum e et la vert est teinte r...

Page 15: ...u un usage hors limites de fonctionnement Dans le cas d un contact accidentel entre du liquide provenant du capteur et la peau ou les yeux il est conseill de laver imm diatement avec de l eau en abond...

Page 16: ...ignote chaque 8 secondes dans ce cas inter rompre la proc dure puis ex cutez le contr le en coupant et en r tablissant l alimentation du d tecteur En cas de persistance il sera n cessaire de remplacer...

Page 17: ...d installation du d tecteur sous 12Vcc La max distanza cui pu essere installato ogni rivelatore dall alimentatore a 24Vcc The maximum distance to install each detector from the 24Vdc power Supply Dist...

Page 18: ...0 ppm 12 30 60 30 ON ON OFF 50 ppm 100 ppm 200 ppm 12 30 60 30 OFF OFF ON TLV TWA COSHH 25 ppm TLV STEL COSHH 35 ppm TLV C 50 ppm 0 0 0 30 ON OFF ON Risevato Reserved R serv Risevato Reserved R serv O...

Page 19: ...Relays Delay Seconds retarde du relais Secondes 1 2 3 ALARM 1 ALARM 2 ALARM 3 ALARM 1 ALARM 2 ALARM 3 FAULT OFF OFF OFF 25 ppm 50 ppm 100 ppm 12 30 60 30 ON OFF OFF 25 ppm 50 ppm 75 ppm 12 30 60 30 OF...

Page 20: ...d R serv Risevato Reserved R serv COSHH Ente Europeo European Department Organisme europ en OSHA Ente Americano U S Department Organisme Etats unien Fig 1 Dimensioni Size Dimensions Fig 2 Schema di co...

Reviews: