85
Load...
Function data can be loaded from the SD card onto the controller or other x2 devices. Multiple func
-
tion data files can be saved to the SD card.
The data transfer is only possible after a technician or expert password has been entered for the tar
-
get device.
After selecting the function data required (*.dat file), you will be prompted to specify how the meter
readings and the heat meter's calibration values should be treated.
You can choose from the following actions:
Selecting
loads the new function data;
cancels the action.
If function data is loaded onto the controller, a _Backup.dat file is created on the SD card with the old
function data.
Once the function data is loaded, the controller returns to the User level.
Retain
The meter readings and calibration values in the controller will be ap
-
plied.
Example of use: After programming is changed using TAPPS2
Reset
The meter readings and calibration values will be reset to zero
Load function data
The meter readings and calibration values applied will be taken from
the function data being loaded onto the controller.
Example of use:
Replacement of a controller. The function data is
taken from the old controller and its meter readings are to be loaded
onto the new controller.