Open customer
An already created customer can be opened in the menu "
File \
Open...
".
Manage customer
Customers can be renamed or deleted via the menu "
File \ Manage...
".
Recording of measured values from a customer system
There are four options for recording the measured values from a customer system:
a)
The C.M.I. (with fixed IP address) is read out
via Internet
.
b)
The C.M.I. is installed with the system and read out
locally
by the service technician
using a notebook.
c)
If customers record the measured values of their system themselves then they can
create a day log file on the SD card in the C.M.I. menu "
Settings / data logging
“ with
"
Create file
“. The folder
LOG
and the file INFOH.LOG are copied to the PC and then
forwarded to the technician
via e-Mail
. The technician enters the data paths of the
folder above in IP/domain in the
Winsol
set-up (without backslash at the end, e.g.
C:\Documents and settings\<User>\My Documents
) and reads the values with "
Read
out logger data
“. The port setting in setup can be ignored here.
d)
If the reading out of the recorded data is
not possible locally
, the measured values
can be recorded as follows:
Preparation for data recording in the C.M.I.:
1)
In the web surface
(menus “Settings/Data logging” and “Settings/Time”), set the de-
sired configuration and the source for the system time.
Data acquisition at the customer:
2)
Connect the prepared C.M.I. to the controller (observe polarity!). In UVR1611 with
output via DL bus the data output must be activated (output 14 -
"Data link“). For
output over the CAN bus, the values to be logged must be
set in the menu “Net-
work/data logging”.
3)
Ensure a reliable power supply: power pack (or CAN bus 12V supply)
4)
During the data logging of controls without a separate system time (e.g. UVR64,
HZR65), "
WEB
" must be set as reference source in the time setting of the C.M.I.
and
an Internet connection must be available.
5)
As long as the C.M.I. is connected with the controller, the measured values are rec-
orded.
Reading out of the recorded data:
6)
Connect the C.M.I. with PC or network via Ethernet.
7)
Ensure a reliable power supply: power pack (or CAN bus 12V supply)
8)
In
Winsol,
create the respective customer for the data to be recorded and carry out
the set-up.
9)
The data stored in the C.M.I.
can now be read in with “
Read out logger
” and then
analysed.