A - Assembly / Installation
• See the main characteristics in the Technical Instructions corresponding to the
TWN
(No. 10 12 172).
• Consult the "Installation instructions" supplied with the control.
• The unit is connected using 0.75mm
2
cable (minimum) (1.5mm
2
max.).
The cables used must comply with the insulation requirements for the voltage used (230 V). This information relates
above all to the sensor input of the automatic control connected to the 230 V supply.
• The temperature adjustment range can be limited using the mechanical limit stops located on the control knob of
RAB
and
RCC
control units.
• Wall mounting.
• Secure the unit at a height of approximately 1.5 m from the floor in a location representative of normal convection
currents, while avoiding:
- wall which are poorly insulated or liable to vibrate,
- the proximity of parasitic heat sources (sunshine, heating appliances, lamps, fireplaces, televisions, etc.),
- currents of air from doors or windows,
- sheltered locations such as shelves or behind curtains,
- near electrical outlets.
• For the
K70P090Z
and
K70P091Z
control, refer to the corresponding technical instructions.
• For manual control
70250076
, check and modify as required the ventilation selection jumper connection SR depending
on the appliance (see below).
• For "
RCC
" type controls (
70250051
and
70250052
), check and modify as required the settings on DIP switches 1 to 8
(located inside the control) depending on the application (refer to the indications below and the controller’s technical
manuals).
B - Connections with manual remote control RAB 30 - code 70250076
• For "2-pipe" or "4-pipe" (or “2-pipe” C electric heater element)
TWN
.
•
Manual
selection of the operating mode (heating or cooling).
• Control by action on the 230 V "On/Off" valve and/or on ventilation.
TWN
70250076
N
U
L
Y1
4
GV
MV
PV
Q1
Q2
Q3
8
9
10
SR2
SR1
SR
Auto
Y2
TWN
70250076
N
U
L
SR2
SR1
SR
Y2
Y1
4
GV
MV
PV
Q1
Q2
Q3
8
9
10
Auto
TWN 2-pipe - Control on a valve
TWN 2-pipe - Control on ventilation
Power supply 230 V / 1 / 50 Hz
Power supply 230 V / 1 / 50 Hz
Position of the SR bridge located inside the controller:
- on
SR1
= Permanent ventilation.
- on
SR2 (Auto)
= Ventilation actuated with the valve.
TWN
70250076
N
U
L
Y2
Y1
4
GV
MV
PV
Q1
Q2
Q3
8
9
10
SR2
SR1
SR
Auto
+
TWN 4-pipe
Control on valves
Power supply
230 V / 1 / 50 Hz
Position of the SR bridge located inside the controller:
- on
SR1
= Permanent ventilation.
- on
SR2 (Auto)
= Ventilation actuated with the valves.
Position of the SR bridge located inside the controller on
SR2 (Auto)
Heating valve
Cooling valve
TWN
70250076
N
U
L
Y2
Y1
4
HS
MS
LS
Q1
Q2
Q3
8
9
10
SR2
SR1
SR
Auto
TWN 2-pipe Cooling
Control on valve and electric heating element
Power supply
230 V / 1 / 50 Hz
Position of the SR bridge located inside the controller:
- on
SR1
= Permanent ventilation.
- on
SR2 (Auto)
= Ventilation actuated with the valve and
electric heating element.
Electric heating element
Cooling valve