background image

16

5-2.  Recommended Wire Length and Diameter

Regulations on wiring diameter differ from locality to locality.

For field wiring requirements, please refer to your local elec-

trical codes. Carefully observe these regulations when carry-

ing out the installation.

Table 7 shows maximum wire lengths for control line and

power line and fuse or circuit capacity.

Refer to the wiring system diagram (Fig. 26a and b) for the

meaning of “A” and “B” in Table 7.

Table 7

NOTE

Cross-sectional

Max. Control Line Length 

Max. Power Line Length 

Fuse 

Area (mm

2

)

(A)

(B)

or 

Model

1.0

2.0

2.6

3.5

Circuit Capacity

GRF194/244MR5IAA                                34 m 15 m 20 m 26 m 20 A

Indoor Unit

Outdoor Unit

Unit A

Unit A

Unit B

Unit B

(A)

Terminal plate (8P)

Terminal plate (3P)

Grounding line

Power supply

Single-phase 
AC 220 – 240 V

(B)

CAUTION

Be sure to connect the

power supply line to the

outdoor unit as shown in

the wiring diagram. The

indoor unit draws its power

from the outdoor unit.

5-3.  Wiring System Diagram

WARNING

Be sure to comply with local codes on running

the wire from the indoor unit to the outdoor unit

(size of wire and wiring method, etc.).

Each wire must be firmly connected.

No wire should be allowed to touch refrigerant

tubing, the compressor, or any moving part.

Be sure to connect power wires correctly match-

ing up numbers on terminals of the outdoor unit

and respective indoor units A – C.

To avoid the risk of electric

shock, each air conditioner

unit must be grounded.

WARNING

Fig. 26a

Fig. 26b

Indoor Unit

Outdoor Unit

Unit A

Unit A

Unit B

Unit C

Unit B

Unit C

(A)

Terminal plate (12P)

Terminal plate (3P)

Grounding line

Power supply

Single-phase AC 220 – 240 V

(B)

2 indoor units with GRF194MR5IAA

3 indoor units with GRF244MR5IAA

Summary of Contents for GRF194MR5IAA

Page 1: ...Required for Installation 2 INSTALLA TION SITE SELECTION 3 2 1 Indoor Unit 2 2 Outdoor Unit 2 3 Outer Dimensions of Outdoor Unit 2 4 Diagram of Outdoor Unit Installation 3 INSTALLATION PROCESS 8 3 1 E...

Page 2: ...king up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut yo...

Page 3: ...utlet or A C workshop 1 4 Type of Copper Tube and Insulation Material If you wish to purchase these materials separately from a local source you will need 1 Deoxidized annealed copper tube for refrige...

Page 4: ...stricted air flow around the unit install the unit within the maximum elevation difference H1 H2 H3 above or below the outdoor unit and within a total tubing length L1 L2 L1 L2 L3 from the outdoor uni...

Page 5: ...n 17 m 6 35 6 35 9 52 Union 12 7 9 52 9 52 A B 94 124 types Outdoor unit Indoor unit 184 type Flare 9 52 Union 12 7 12 7 Flare 9 52 A joint for connecting tubes of different sizes More than 17 m Fig 2...

Page 6: ...52 C 94 124 types Outdoor unit Indoor unit 94 124 types 184 type Less than 17 m 6 35 6 35 9 52 9 52 9 52 6 35 9 52 A 9 52 B 9 52 C 94 124 type Outdoor unit Indoor unit 94 124 type 94 124 type GRF244MR...

Page 7: ...will not magnify operating noise or vibration Fasten in place with the anchor bolts M10 provide a base using concrete or similar material and ensure proper drainage select a location where there is n...

Page 8: ...ure below are spaces that are required in order to maintain performance Install in a location where the dimensions indicated by are ensured and where 2 or more faces of the unit are unobstructed In pr...

Page 9: ...own and pull it toward you Refer to 2 4 Diagram of Outdoor Unit Installation 3 Remove the tubing panel in order to attach covers as needed according to the number of indoor units Refer to 2 4 Diagram...

Page 10: ...ngth 3 5 Caution before Connecting Tubes Tightly a Be sure to apply a sealing cap or water proof tape to prevent dust or water from getting into the tubes before they are used b Be sure to apply refri...

Page 11: ...1 clamp approx every 120 cm Do not wind the armoring tape too tightly since this will decrease the heat insulation effect Also be sure the condensation drain hose splits away from the bundle and drip...

Page 12: ...is cycle is repeated until the room temperature is lowered to the target level During the heating cycle the direction of refrigerant flow is reversed by a 4 way valve As a result the condenser draws h...

Page 13: ...th pressure gauges to the service port on the Hi Lo B A C Service valve on narrow tube side Service valve on wide tube side With push pin Hex wrench nominal size 4 mm not provided Manifold gauge speci...

Page 14: ...in 6 With a hex wrench turn the valve stem on the nar row tube service valve counter clockwise by 90 degrees 1 4 turn for 10 seconds and then turn the stem clockwise to close it again 7 With a standar...

Page 15: ...le at the outdoor unit This work must be performed during cooling operation The refrigerant gas cannot be recovered during heating operation During winter or if the temperature sensor prevents cooling...

Page 16: ...nstructions 5 1 General Precautions on Wiring 1 Before wiring confirm the rated voltage of the unit as shown on its nameplate then carry out the wiring closely following the wiring diagram 2 Provide a...

Page 17: ...ly Single phase AC 220 240 V B CAUTION Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram The indoor unit draws its power from the outdoor unit 5 3 Wiring Syst...

Page 18: ...ature sensor Humidity sensor BK BK Black W White R Red GRN Green Y Yellow BL Blue GY Gray Fig 27a INDOOR UNIT BK BK Control panel Terminal board Display receiver panel GRN Fan motor Flap motor W W W W...

Page 19: ...7 9 CN35 WHT 3 1 5 SI BRN TERMINAL BASE 3P 6 6 7 7 WHT BLK WHT PAM PAM CN23 4 4 5 5 WHT BLK WHT 1 1 2 2 BLK BLK WHT CT CT WHT CN08 1 1 3 3 BLK BLK WHT PRY PRY RED CN21 W W AC200 L2 CN29 BLK YEL YEL BL...

Page 20: ...PCB HS ORG 7 9 CN35 WHT 3 1 5 SI BRN TERMINAL BASE 3P 6 6 7 7 WHT BLK WHT PAM PAM CN23 4 4 5 5 WHT BLK WHT 1 1 2 2 BLK BLK WHT CT CT WHT CN08 1 1 3 3 BLK BLK WHT PRY PRY RED CN21 W W AC200 L2 CN29 BLK...

Page 21: ...it on the termi nal plate and fix it securely with the removed ter minal screw using a screwdriver For stranded wiring 1 Cut the wire end with a cutting pliers then strip the insulation to expose the...

Page 22: ...iring Instructions for the Outdoor Unit The below explanation uses model GRF244MR5IAA as an example With model GRF194MR5IAA there is no terminal block C Be sure to correctly align inter unit cables A...

Page 23: ...h unit If there is cold air mixed in with the warm air check the tubing connections again Checking tubing and wiring Perform the test run and check that operation is nor mal If there is an error in tu...

Page 24: ...tubing connections Drain connections are secure and water drains properly Putty has been used to close the hole in the wall All service valves are fully open Remote controller signals are being posit...

Reviews: