6
Symbol of indoor unit SEE OUTDOOR UNIT INSTALLATION INSTRUCTION
Power Source
220 – 240 V ~ 50 Hz
Cooling
Max.Capacity
kW
9.80
BTU/h
33800
Indoor unit(s)
A + B
C
A + B + C
Capacity
kW
5.50
4.3
9.8
BTU/h
19000 15000 33800
Voltage rating
V
230
Available voltage range
V
198 to 264
Running amperes
A
10.9 9.5 19
Power input
W
2350 2000 4050
Power factor
%
94
92
93
C.O.P.
W/W
2.4 2.2 2.4
Compressor locked rotor amperes
A
45 / 46 / 48
41 / 43 / 45
86 / 89 / 93
Fan speed
2
Compressor
Rotary (Hermetic)
Refrigerant / Amount charged at shipment
g
R407c / A + B : 1,300 C : 1,200
Refrigerant control
Capillary tube
Operation sound
dB-A
54
Refrigerant tubing connections
Flare type
Max. allowable tubing length at shipment
m
A + B : 15 C : 7.5
Refrigerant tube
Narrow tube
mm (in.)
A , B , C : 6.35 (1/4)
diameter
Wide tube
mm (in.)
A , B : 9.52 (3/8) C : 12.7 (1/2)
Refrigerant tube kit
Optional
Dual system kit
Non
GRV340M3C5
Unit dimensions
Height
mm
1,235
Width
mm
940
Depth
mm
340
Package dimensions
Height
mm
1,343
Width
mm
1,036
Depth
mm
421
Weight
Net
kg
108.0
Shipping
kg
116.0
Shipping volume
m
3
0.59
Dimensions & Weight
Features
Electrical Rating
Performance
Outdoor Unit GRV340M3C5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.