DSAFP
37
●
Fig. 3-62 shows an example of installation.
Air outlet duct
Air-outlet grille
Ceiling material
Indoor unit
Bolt anchor
Suspension bolt
Air-intake duct
Air-intake grille
Fig. 3-62
Fig. 3-63
Fig. 3-64
Drain hose
(supplied)
(not supplied)
(not supplied)
Packing (supplied)
VP-25
Align the hose band with end of the
hose, and tighten so that it does not
contact the bead.
Drainage check
section on drain port
(transparent)
Hard PVC
socket VP-25
Hard PVC
pipe
PVC adhesive
Bead
Vinyl clamps
Drain insulator (supplied)
3-20. Installing the Drain Piping
(1) Prepare standard hard PVC pipe (O.D. 32 mm) for
the drain and use the supplied hose band to pre-
vent water leaks.
The PVC pipe must be purchased separately.
The transparent drain part on the unit allows you
to check drainage. (Fig. 3-63)
CAUTION
●
Do not use adhesive at the
drain connection port on
the indoor unit.
●
Insert the drain pipe until it
contacts the socket, as
shown in the figure at right,
then secure it tightly with
the hose band.
●
Do not use the supplied
drain hose bent at a 90°
angle. (The maximum per-
missible bend is 45°.)
●
Tighten the hose clamps so
their locking nuts face
upward. (FIg. 3-63)
(2) After connecting the drain piping securely, wrap
the supplied packing and drain pipe insulator
around the pipe, then secure it with the supplied
vinyl clamps. (Fig. 3-64)
Make sure the drain pipe has a downward gradient
(1/100 or more) and that there are no water traps.
NOTE
04-393 DC INV Tech p a-44 12/15/04 3:05 PM Page 37