Antipassback function 

This function is implemented since the FW version 5.0. 

The Antipassback function is defined in two ways: 

 

Time APB

 

– user cannot repeatedly use his ID for defined time 

 

Zone APB

 

– user cannot repeatedly enter an area, where he is already present 

The  Antipassback  function  is  used 

only  for  the  users

,  whose  access  is  driven  by  a 

time

 

schedule

.  The  users  with  access  always  granted  are  not  affected  by  the  Antipassback 

function. 

The  Antipassback  flags  for  an 

ID

  can  be 

reset

  by 

inserting  the  ID  again

  with  use  of  the 

programming  cards

  (offline  solution). 

All  Antipassback  flags

  are  also 

reset

  whenever  new 

access rights data are downloaded

 from the program. 

Both Zone and Time Antipassback flags are written either immediately 

after an ID is read

, or 

after relevant 

door is opened

 (relevant input is disconnected). 

6.10.1  Time Antipassback 

The 

Time

 

Antipassback

 is defined by the 

ABP

 

timer

 

initial

 

value

 (in minutes), which is set to 

the ID after passing at the reader module. If the users uses the ID at the address during the 
timer for the ID is running, the Time APB alarm is raised. Following parameters affect the 
Time APB function: 

 

APB  timer  initial  value

 

–  defines  the  Time  APB  flag  (timer)  value  set  to  the  ID  after 

passing at the reader module. If a user uses the ID again before the timer elapses, Time 
APB alarm is raised. 

 

Open door after APB time alarm

 

– if the option is enabled, the Door open function is 

performed after the Time APB alarm is raised. 

6.10.2  Zone Antipassback 

The 

Zone Antipassback

 is defined by 

enabling the option

 for the relevant address. The Zone 

APB flag is set for the ID when passing at the  reader module. If a user uses the ID again 
when the Zone APB flag is set, the Zone APB alarm is raised. Following parameters affect 
the Zone APB function: 

 

Enabled 

– enable/disable general Zone APB flag setting. 

 

Enable in offline mode 

– if the option is not set, the module operates in offline mode like 

if the APB function was not implemented. 

 

Open door after APB Zone alarm 

– if the option is enabled, the Door open function is 

performed after the Zone APB alarm is raised. 

 

 

Summary of Contents for 53465000

Page 1: ...65 APS mini Plus reader modules User s guide 2004 2019 TECH FASS s r o V t nsk 1611 19 153 00 Prague Czech Republic www techfass cz techfass techfass cz Date of release 2019 06 03 valid for FW version...

Page 2: ...s 6 4 5 Mounting and removal the module 7 5 Setting parameters of the reader module 8 5 1 Configurable parameters 8 5 2 Reader module parameters setting 8 6 Reader module functioning 9 6 1 Door Open f...

Page 3: ...e of the APS mini Plus system In effect the number of lines is not limited The reader module is designed both for outdoor and indoor use 2 1 MREM 65 BK reader module The MREM 65 BK modules are deliver...

Page 4: ...N A ID technology typical reading range EM Marin 8 cm with ISO card Real time clock Yes with 24 hrs back up Memory Cards 2 000 ID 2 programming cards Events 3 400 Time schedules 64 Inputs 1st input L...

Page 5: ...working in standard operating mode The module must be paired with appropriate reader module before use 3 5 Mechanical design Mechanical design Weight 0 202 kg Operating Temperature 25 60 C Humidity Ma...

Page 6: ...ng mode Fast switching red green Address setting mode RS 485 BUS testing mode Single flash green ID media reading D2 Yellow Continuously lit flashing Programming mode Short flashing with 1s per Indica...

Page 7: ...o relevant fasteners see Pic 3 Then set the housing on the upper part of the base and rotate the housing until the both parts snaps down It is recommended to place an installation box for connection o...

Page 8: ...s Acoustic signalization time Forced door 0 255 s 30 s Acoustic signalization time Door ajar 0 255 s 0 s Acoustic signalization time APB alarm 0 255 s 0 s Signalization time Card alarm 0 255 s 30 s An...

Page 9: ...hed and the beeper is activated when not disabled when the Door Open function is activated The beeper stays active until the door is opened or the preset door lock release time has elapsed see configu...

Page 10: ...ith setting of the signaling timer 0 occurs the alarm output is activated It can control any alarm device directly or it can be processed further After terminating all alarm conditions the alarm outpu...

Page 11: ...er module s memory when the module goes online When a programming card is read while in either online or offline mode the module goes into programming mode 6 5 Read ID media format 6 5 1 EM Marin ID m...

Page 12: ...erating mode Since the FW version 5 09 the reading synchronization of a couple of TECHFASS readers is implemented enabling to cancel the mutual disturbance of the modules The reader module offers the...

Page 13: ...for inserting the reader goes into programming mode One by one read the cards which are to be granted access About 15 seconds after inserting the last card the reader module goes back into standard o...

Page 14: ...s into programming mode which is indicated by slow flashing of yellow LED Read the programming card for inserting 5 times in a row the reader will go into Deleting cards above or below mode indicated...

Page 15: ...adding and deleting cards should be stored in the table Following example shows correct usage of the programming cards and proper filing of the actions Inserting 5 new cards using the procedure from c...

Page 16: ...eleting all cards using the procedure described in chapter 6 7 4 it is necessary to create a new filing table 6 8 ID expiration function This function is implemented since the FW version 5 0 It is pos...

Page 17: ...to the ID after passing at the reader module If the users uses the ID at the address during the timer for the ID is running the Time APB alarm is raised Following parameters affect the Time APB functi...

Page 18: ...Remote identification with ID is disabled for users with access driven by a time schedule The disabling status changes and disabled actions are logged in the events archive 6 12 Reading synchronizati...

Page 19: ...lock diagram for access right evaluation can be seen in Pic 6 Pic 6 Simplified access rights evaluation VALID UNKNOWN ID FOUND ACCESS DRIVEN BY TIME SCHED ACCESS ALWAYS GRANTED HOLIDAY ACCESS GRANTED...

Page 20: ...er 51900200 and attach it in the hole with appropriate mastic to ensure the top surface of the magnet matches with the wall surface Mount the reader module in formerly prepared holes mounted with plug...

Reviews: