TECH ST-402N PWM User Manual Download Page 22

ST-402N User's Manual v 1.0.3

 

22

 -

 

V.f.3) 

 

Heater 

The  heater  is  used  to  electrically  heat  the  tank.  The  principle  of  operation  is  similar  to  that  in  the 
previous case but the heater should be connected by means of an additional contactor. The user sets 
the  activation  delta  (the  difference  between  the  tank's  set  temperature  and  the  tank's  current 
temperature), below which the controller will activate the heater. Then, the user selects the time interval 
in which the electric heating function will be active (by means of the "

From

" and "

To

" functions). 

 

 

 

V.f.4) 

 

Contact (not) Consistent with Pump 

This setting determines the operation of the voltage-free contact. If the icon "Contact Consistent with 
Pump"  is  marked,  then  the  voltage-free  contact  will  close  always  when  the  pump  operates  (the 
additional device will activate). Otherwise (when the icon is unmarked), the contact will open at each 
activation of the solar pump.

 

 

V.f.5) 

 

Cooling with DHW Pump 

Option inactive in the case of setting the installation scheme number: 5, 8, 11, 13 and 15.

 

 

This is a function which operates beyond a time interval, namely all the time. Sensor 4 is required 

for it to operate (installed in the external DHW Tank). This function may not operate when a scheme 
using all sensors is selected. Furthermore, a tank sensor is needed for it to operate (in the case of two 
sensors in the tank - the top sensor)

 

If the criteria referred to above are met, the peripheral will be activated (contact closing) when:

 

 

The tank's temperature during its growth exceeds its maximum temperature  reduced by the 

"Cooling  Activation  Delta"  and  operates  until  the  temperature  drops  below  the  tank's  maximum 
temperature reduced by the "Cooling Deactivation Delta" (both parameters are adjusted in the menu).

 

 

The temperature in the tank is higher than the DHW Temperature. A constant hysteresis of 3 

degrees is used here.

 

 

V.g) 

 

Calculation of Energy

 

Entering the following values correctly will make it possible for measure the gained energy in a more 
precise manner.

 

 

V.g.1) 

 

Flow 

At this point, the user should specify the quantity of glycol that flows through the pump in one minute.

 

 

V.g.2) 

 

Type of Agent 

This function allows the user to identify the agent used: ethylene glycol, propylene glycol or water.

 

 

V.g.3) 

 

Glycol Solution 

At this point, the user should specify the percentage concentration of glycol in water.

 

 

V.g.4) 

 

Calibration 

This  function  allows  the  user  to  calibrate  the  difference  in  temperatures  between  the  sensors.  The 
temperature  measurement  takes  place  in  the  temperature  sensor's  installation  place.  There  is  a 
possibility of deviations in the flow and temperature measurement at the return from the container. 
The manufacturer does not recommend changing this setting.

 

Summary of Contents for ST-402N PWM

Page 1: ...Tech 1 User s manual ST 402N PWM...

Page 2: ...ure the regulator is disconnected from the mains before perform ing any activities involving the power supply plugging cables installing the device etc The device should be installed by a qualified el...

Page 3: ...l signal relay is necessary to control the heater III Principle Of operation Description of the Control Panel of a Sample System Opis panelu steruj cego przyk adowego uk adu The regulator is controlle...

Page 4: ...Active Operation Mode The Symbol of Active Additional Device Peripherals Automatic Operation Mode Circulation Pump Collector Defrosting Mode Firing up the Pellet Boiler voltage free signal Holiday Mo...

Page 5: ...VICE MENU Pumps Solar Pump Deactivation Delta in this case the pump will be activated again when the temperature on the collector increases above the tank s temperature by the Solar Pump Activation De...

Page 6: ...of activating the disinfection the temperature of disinfection needs to be reached in no longer than the time defined by the user SERVICE MENU Peripherals Heater Anti Legionella Maximum Anti Legionel...

Page 7: ...ction of property IV h Statistics The parameters in this submenu allow the user to monitor the current conditions of the controller s operation IV h 1 Gain This parameter allows the user to monitor th...

Page 8: ...essing the Menu button In order to return to the display s main view exit the service menu the user should use the Exit button by pressing it several times or waiting for approx 30 seconds the device...

Page 9: ...Time Anti Freeze Temperature Collector Delta Heat receiver Receiver Maximum Temperature Receiver Activation Temperature Heat Receiver Hysteresis Pumps Regulated Revolutions Collector Maximum Temperat...

Page 10: ...al peripherals Installation Sensors The Collector s sensor The Accumulation Tank s sensor V a 2 Scheme 2 17 One Tank Order Installation 2 17 Operates The Collector Pump The Switching Valve top bottom...

Page 11: ...not possible to cool down using the DHW pump Installation Sensors The collector s sensor The two sensors of the Accumulation Tank top and bottom The boiler temperature sensor Additional Parameters to...

Page 12: ...k s pump Tank 1 with top and bottom circulation Tank 2 One direction of the collectors location Additional peripherals not possible to cool down using the DHW pump Installation Sensors The collector s...

Page 13: ...irculation If the tank s temperature is too low the valve switches to the furnace Additional Parameters to be Adjusted additional submenu in the service menu Installation s Options reheating deactivat...

Page 14: ...ta of pump 2 Activation delta of pump 2 V a 13 Scheme 13 17 Two Collectors Pump Valve Tank and Additional Tank Connected in Series Installation 13 17 Operates The Collector Pump The Switching Valve Th...

Page 15: ...ce the submenu Peripherals is hidden in the controller s service menu The switching valve operating the additional receiver is connected instead of the peripherals Additional parameters to be adjusted...

Page 16: ...eiver receiver maximum temperature receiver activation temperature heat receiver hysteresis V b Accumulation Tank This menu allows the user to adjust all parameters related to the tank heat container...

Page 17: ...e of scheme 6 the setting relates to valve control when cooling the Collector down in the Summer Mode or Alarm Mode as well as when defrosting The valve hysteresis determines the difference in tempera...

Page 18: ...minimum reheating temperature the pump is deactivated On the other hand when the temperature on the collector is below this limit and is increasing the pump is activated after reaching the minimum reh...

Page 19: ...r declares the value of the collector s maximum alarm temperature when the pump may be damaged This temperature should be adjusted according to the collector s technical data Due to phenomenon of glyc...

Page 20: ...hes to circulation 2 and the pump operates in operation cycles parameter Maximum Heating Time of Tank 2 as well as pause Parameter Oscillation Pause Time When the collector reaches a high enough tempe...

Page 21: ...n NO deactivate Additional available devices and examples of connections supporting all available installation schemes are presented below In the case of using schemes 12 or 14 it is not possible to c...

Page 22: ...rthermore a tank sensor is needed for it to operate in the case of two sensors in the tank the top sensor If the criteria referred to above are met the peripheral will be activated contact closing whe...

Page 23: ...ve in the case of setting the installation scheme number 5 and 11 This parameter is used to adjust the threshold tank temperature at which the valve will switch to reheating the boiler s return V h 5...

Page 24: ...free operation the regulator has been equipped with a range of safeguards 1 Installation Sensor Protection If one of the sensors is damaged an acoustic signal is activated and the following symbol wil...

Page 25: ...its cables The user should also check if the controller is properly mounted and clean it if dusty or dirty Technical Data of ST 402N Controller Power Supply Voltage 230V 50Hz 10 Temperature Adjustment...

Page 26: ...not replace the design of the CH installation It is aimed at demonstrating the possibility for expanding the controller The presented scheme of the heating installation does not contain cut off and pr...

Page 27: ...t 7 IV h 3 Power Supply Failures 7 IV i Backlight 7 IV j Display Contrast 7 IV k Language 7 IV l Information 7 IV m Factory Settings 8 V Service Menu 8 V a Installation Scheme 10 V a 1 Scheme 1 17 Bas...

Page 28: ...7 V b 10 Hysteresis of Tank 2 17 V b 11 Operation Algorithm 17 V b 12 Tank Reheating Priority 18 V c Solar Collector 18 V c 1 Overheat Temperature 18 V c 2 Minimum Reheating Temperature 18 V c 3 Anti...

Page 29: ...Type of Agent 22 V g 3 Glycol Solution 22 V g 4 Calibration 22 V h Installation Options 23 V h 1 Reheating Activation Delta 23 V h 2 From Hour to Hour 23 V h 3 Energy Release 23 V h 4 Energy Release...

Page 30: ...Voltage Directive LVD 2006 95 EC the Act dated April 13th 2007 on electromagnetic compatibility Journal of Laws 07 82 556 implementing the provisions of Directive EMC 2004 108 EC as well as the Regul...

Page 31: ...y number assigned by the Main Inspector of Environmental Protection The symbol of a crossed out rubbish bin on a product means that the product must not be thrown out to ordinary waste bins By segrega...

Page 32: ...ST 402N User s Manual v 1 0 3 32...

Reviews: