Capacity
6KVA
8KVA 10KVA 12KVA 15KVA 20KVA 25KVA 30KVA
Internal protection equipment and LCD panel
Battery
UPS automatically shutdowns when battery is low power level, there is
no fuse switch protection.
Overload
When load reaches 110~150% of rating, transfer to bypass after 30s,
recover auto after unload.
Over-temperature
Automatically transfer to bypass if UPS internal temperature > 85
℃
Output
short-circuit
Limit current, automatic shutdown, fuse and there no fuse switch
protection.
UPS abnormal
Automatically transfer to bypass and supplied power by utility
Noise filter
10~100KHz at 40Db; 100KHz~100MHz at 70dB
LCD display
input, output voltage, frequency, battery voltage, output power (%),
temperature
Battery BVL
One LED, it lit on when battery low voltage
Environment
Temperature
0~40
℃
Humidity
0~95%, non-condensing
Noise
<58dB (1m)
General
Output socket
Terminal plate
Unit weight
118Kg 128Kg 155Kg 165Kg 262Kg 297Kg 326Kg 336Kg
Dimension (mm)
305×585×864
725×430×1180
others
Full efficiency
>85%
Transform time
0ms
UPS status
indicator
Utility, inverter, bypass, UPS abnormal (fault)
Communication
interface
RS232 interface of DB9 model