UPS will sound alarm every 1s again when battery power is to be exhausted.
5. Utility indicator light will be on when UPS input power source is resumed.
Plug the LCD display cycle switch button to switch items displayed, see if
display value is normal, thus first start-up procedure has been completed.
Please measure output voltage and see if it meets the requirement, then connect
load to UPS output terminal. Use pure power provided by UPS formally.
6. After connect load, plug LCD display cycle switch button to switch items
displayed till display the item of output power display percent %. If the value
displayed is more than 100%, please dismantle the unimportant load till the
value displayed is less than 100%.
6.3 Daily switch ON/OFF operation procedure
If you want to switch on/off during daily using, please operate UPS according
to the following ways:
1. If you want to switch off UPS, you can switch off UPS by plugging the
“OFF’ button located on front panel. At the time UPS is under bypass condition,
utility supplies power to output and the batteries are under charging condition.
2. Always turn on UPS by plugging down the “OFF’ button when daily
operation.
6.4 Switch ON/OFF operation procedure when UPS hasn’t been will be
not used for long-time.
1. If the time in during UPS will be not used exceeds ten days, please first turn
off UPS by pushing the “off” button on front panel, then position the NFB on
back panel the position of “OFF”.
2. If the time that UPS doesn’t be used exceeds three months, please run UPS
for above 24 hours according to the process of first start-up and make the
battery on the full electrical position and extend battery life.