TPF45000-385 

POWER SUPPLY 

OPERATION MANUAL

 

15 

 

3 February 2022 

PMBus COMMAND SET 
 

 

OPERATION MODE 

 
This command is used to set the way you control the output of the  TPF45000-385.  Setting the Operation Mode to “

Remote 

Mode

” 

allow you to control the output using the “OPERATION ON/OFF” command via the I

2

C

 only. 

 In the “

Local Mode

” 

you can control the output using the “PSON” pins on the Signals connector only. 

The default is the “

Local Mode

”. 

 

 

Command code

 

Type

 

Data sent

 

D8h 

R/W Byte 

00h=Remote 

D8h 

R/W Byte 

80h=Local 

 
 

 

OPERATION (ON/OFF) 

 
If the TPF45000-385 is turned OFF with the “

OPERATION OFF

” command, it can be turned ON with the “

OPERATION 

ON

” command. 

 

 

Command code

 

Type

 

Data sent

 

01h 

R/W Byte 

00h=OFF 

01h 

R/W Byte 

80h=ON 

 

Note: 

This command will not work in the 

Local Mode

”.

 

 

 

CLEAR_FAULTS 

 
This command is used to clear the “STATUS REGISTERS” after any fault occurs. 
If the CLEAR_FAULTS command is not sent after any fault occurs, the “STATUS REGISTERS” will not be cleared.  
ALERT signal will remain “LOW” until a “CLEAR_FAULTS” command is sent. 
If a Fault or Warning is still present after “CLEAR_FAULTS” is sent, “STATUS REGISTERS” will be updated and the 
ALERT signal will be “LOW” again. 
 

 

Command code

 

Type

 

#Data bytes

 

03h 

Send Byte 

 
 
 
 
 
 
 
 
 
 
 

 

 

 

Summary of Contents for TPF45000-385

Page 1: ...2 Ratings Specifications and Features 4 Emissions 4 Immunity 4 Maximum Ratings 5 Input Specifications 5 Output Performance Specifications 6 Protective Functions 6 Operating Modes 6 Status Indicators 7...

Page 2: ...iring terminals The appliance must be securely mounted and the Ground Stud properly bonded to the main protective earth contact before any connection to AC mains supply is made The ventilation opening...

Page 3: ...ing burning or other damage might occur to the unit The output voltage of this power supply unit is considered to be a hazardous energy level The voltage is 2V or more and the electric power is 240VA...

Page 4: ...urge IEC61000 4 5 2005 4kV common mode 2kV differential mode Conducted RF Common Mode EN61000 4 6 2009 150 kHz 80 MHz at 3 Vrms 1 kHz 80 amplitude modulated Power Frequency Magnetic Field IEC61000 4 8...

Page 5: ...rent Power allowable between 380VAC and 504VAC input 3 Critical Note If minimum load is not present while the unit is inhibited the output can slowly be charged to unsafe levels DO NOT remove output l...

Page 6: ...otective Functions Units OCP TYPE Foldback with delayed shutdown latch Manual reset by input cycling or remote control via the PMBus Interface OCP KNEE POINT 116A KNEE POINT PROTECTION NONE NO DAMAGE...

Page 7: ...the unit and the output is OFF b One or more of the Fans is rotating slow or not working at all c DC Buss in one or more of the power modules is out of limit d OTP Condition e The unit is turned OFF v...

Page 8: ...he PMBus Factory Programmed Manufacturer ID Model Revision Manufacturer location Manufacturing Date and Serial Number Table 9 Input Output and Signal Connections Input 4 Pin connector Recommended mati...

Page 9: ...for Return FAULT ALARM 7 Conducts when Fault occurs Open collector Non Polarized 60V peak Max sink current 5mADC 2 ON resistance Isolated Terminal 5 used for Return DC OK 8 Conducts when Vout is grea...

Page 10: ...TPF45000 385 POWER SUPPLY OPERATION MANUAL 10 3 February 2022 Figure 1 Pin assignments...

Page 11: ...e connected in parallel at 30cm from the output terminals along the load cable Attach a maximum 1 5m 50 coaxial cable from the ceramic capacitor electrodes to a filter attachment installed on the osci...

Page 12: ...2022 Mechanical Drawing Overall dimensions for the TPF45000 385 is shown below The unit weight is approximately 30 kg and should be installed onto a shelf or support bracket rails Secure in place usin...

Page 13: ...cale above 50 load Monitoring the Output Voltage Monitoring the Internal Temperature For reference only no accuracy specified Programming the Output ON OFF Reading and Clearing Faults Reading the Manu...

Page 14: ...4 possible addresses A6 A5 A4 A3 A2 A1 A0 R W Byte Hex Address 0 1 0 0 0 0 0 x 40h 0 1 0 0 0 0 1 x 42h 0 1 0 0 0 1 0 x 44h 0 1 0 0 0 1 1 x 46h In case more than one unit is connected to PMBus each uni...

Page 15: ...Local OPERATION ON OFF If the TPF45000 385 is turned OFF with the OPERATION OFF command it can be turned ON with the OPERATION ON command Command code Type Data sent 01h R W Byte 00h OFF 01h R W Byte...

Page 16: ...y 0 Faults Type Bit in Status Register Meaning Output behavior ON OFF FAULT 0 Global Output Enabled Output Disabled Output ONor OFF OTW WARNING 1 Internal temperature 10 C below OTP limit Output ON OT...

Page 17: ...ule 1 in OTP condition 2 1 Internal temperature of Module 2 in OTP condition 3 2 Internal temperature of Module 3 in OTP condition 4 3 Internal temperature of Module 4 in OTP condition 5 4 Internal te...

Page 18: ...1 0 Output Voltage 85 95 of Set Vout on Module 1 2 1 Output Voltage 85 95 of Set Vout on Module 2 3 2 Output Voltage 85 95 of Set Vout on Module 3 4 3 Output Voltage 85 95 of Set Vout on Module 4 5 4...

Page 19: ...ted by 1 Module Bit in 1st Byte Meaning 1 0 One InputPhase Low or Out on Module 1 2 1 One InputPhase Low or Out on Module 2 3 2 One InputPhase Low or Out on Module 3 4 3 One InputPhase Low or Out on M...

Page 20: ...FANOK Bit in the STATUS REGISTER of the TPF45000 385 Command Used Type Data bytes DFh Read Byte 1 Fan in Fault is indicated by 1 Module Bit Meaning 1 0 Fan 1 is rotating slow or Stopped 2 1 Fan 2is ro...

Page 21: ...ed Type Data bytes DEh Read Word 2 Module in Disable Mode is indicated by 1 Module Bit in 1st Byte Meaning 1 0 Vout of Module 1 Disabled 2 1 Vout of Module 2 Disabled 3 2 Vout of Module 3 Disabled 4 3...

Page 22: ...te Example Assume the data received is 0x03 0x45 03 69 3 255 69 834Hrs COMMANDSTO READ MANUFACTURING INVENTORY DETAILS Command Name Commandcode Type Data bytes PMBUS_REVISION 98h Read Byte 1 MFR_ID 99...

Page 23: ...age monitoring V 225 300 353 28233 2 Output Voltage monitoring V 0 385 25575 0 4 Output Current monitoring 0 110 100 0 0 Temperature monitoring C 0 150 23 4750 1 m b R coefficients can also be recover...

Page 24: ...ed Output voltage of the TPF45000 385 Command Used Type Data bytes 8Bh Read Word 2 READ_Iout This Command is used to retrieve the measured Output Load Current of the TPF45000 385 Command Used Type Dat...