TPF45000-385
POWER SUPPLY
OPERATION MANUAL
18
3 February 2022
READ_DC_STATUS
This Command is used to determine which of the 10 modules inside the TPF45000-385 set the Output Fault (DCOK) Bit
in the “STATUS REGISTER”.
Command Used
Type
#Data bytes
DCh
Read Word
2
Module in Fault is indicated by “1”.
Module
Bit # in
1
st
Byte
Meaning
1
0
Output Voltage < 85~95% of Set Vout
on Module #1
2
1
Output Voltage < 85~95% of Set Vout
on Module #2
3
2
Output Voltage < 85~95% of Set Vout
on Module #3
4
3
Output Voltage < 85~95% of Set Vout
on Module #4
5
4
Output Voltage < 85~95% of Set Vout
on Module #5
6
5
Output Voltage < 85~95% of Set Vout
on Module #6
7
6
Output Voltage < 85~95% of Set Vout
on Module #7
8
7
Output Voltage < 85~95% of Set Vout
on Module #8
Module
Bit # in
2
st
Byte
Meaning
9
0
Output Voltage < 85~95% of Set Vout
on Module #9
10
1
Output Voltage < 85~95% of Set Vout
on Module #10