94
83532002 Rev H
9.3. Isolated Programming & Monitoring Connector
Refer to Table 9-1 for a detailed description of the rear panel Isolated Programming &
Monitoring connector. To provide the lowest noise performance, it is recommended to use
shielded-twisted pair wiring.
Refer to Fig.9-1 for description of the connector.
Isolated programming plug P/N: MC1.5/8-ST-3.81, Phoenix.
Table 9-1: Detailed Description of Isolated Programming & Monitoring Connector
Terminal
Signal name
Function
Range 0-5V/0-10V
IS510 option
Range 4-20mA
IS420 option
1
SHLD
Shield, connected internally to chassis
of the power supply.
Chassis ground
2
+VPROG_ISO
Output Voltage Programming input
0-5V/0-10V
4-20mA
3
+IPROG_ISO
Output Current Programming input
0-5V/0-10V
4-20mA
4
GND_ISO
Ground for programming signals.
Ground
Ground
5
GND_ISO
Ground for programming signals.
Ground
Ground
6
+VMON_ISO
Output Voltage Monitoring output
0-5V/0-10V
4-20mA
7
+IMON_ISO
Output Current Monitoring output
0-5V/0-10V
4-20mA
8
SHLD
Shield, connected internally to chassis
of the power supply.
Chassis ground
1
2
3
4
5
6
7
8
Shield
+VPROG_ISO
+IPROG_ISO
GND_ISO
Shield
+IMON_ISO
+VMON_ISO
GND_ISO
Fig. 9-1: Isolated Programming & Monitoring connector