DC Inverter Air
shall be paid to that the saw dust cannot enter the pipeline);
3) The flaring tool shall be used and the size of flare opening shall remain as follows:
Do not forget to consider the pipe nut in the situation specified for processing of flare opening.
Shape and Size of Flare Opening:
Dimension table (unit: mm)
Nominal size
Outer diameter D
0
A
F1/4
6.35
8.6‐9.0
F3/8
9.52
12.6‐13.0
F1/2
12.7
15.8‐16.2
F5/8
15.88
19.0‐19.4
F3/4
19.05
22‐22.4
Attention shall be paid to that the bore diameter of pipe nut shall be increased by 1mm based on the
dimension A; otherwise there is a possibility that the pipe nut cannot be assembled.
Pipe diameter “d”
(
mm
)
6.4
9.5
12.7
15.9
19.1
R22 flare size “A”
(
mm
)
8.8
12.8
16.2
19.4
23.7
R410A flare size “A”
(
mm
)
9.1
13.2
16.6
19.7
24.0
Notes: A. The flared side of R410A is deeper than that of R22;
B. The eccentricity between horn center and pipe center is set for 0.1mm or above;
C. There shall be no scar, crack and asperity at the horn position.
4)
Apply the air‐conditioning oil on the inner and outer surface of the flare (for facilitating the smooth pass
of flare nut to prevent the distortion of the pipeline)
A.
Carefully remove the burrs;
B.
Use two wrenches to grab the pipe;
C.
The flare nut shall be mounted onto the pipe before the pipe expansion operation;
D.
The torque force shall be appropriate when using it to tighten the nut (standard torque ±10
%
)
Size
Torque
(kgf ∙m)
(N∙cm)
1/4"(Φ6.4)
144‐176
1440‐1720
3/8"(Φ9.5)
133‐407
3270‐3990
1/2"(Φ12.7)
504‐616
4950‐6030
5/8"(Φ15.9)
630‐770
6180‐7540
3/4"(Φ19.0)
990‐1210
9270‐11860
72
/
113
Summary of Contents for ITCA-60CHRA/DV3I
Page 1: ...Technical Manual for DC Inverter Air Conditioner 1 113...
Page 13: ...DC Inverter Air 1 4 Electrical Wiring Diagram 13 113...
Page 14: ...DC Inverter Air 1 5 Air Velocity and Temperature Distributions Airflow velocity 14 113...
Page 22: ...DC Inverter Air 22 113...
Page 28: ...DC Inverter Air 2 3 Service Space 2 4 Wiring Diagrams 28 113...
Page 41: ...DC Inverter Air 3 2 Wirin g Diagra ms 41 113...
Page 42: ...DC Inverter Air A irflow velo city Discharge angle 60 FLOOR 42 113...
Page 43: ...DC Inverter Air Airflow velocity Temperature 43 113...
Page 64: ...DC Inverter Air 7 2 Electrical Wiring Diagram 2 1 TCA 36HRA DV 64 113...
Page 65: ...DC Inverter Air 2 2 TCA 48H RA DV3 TCA 60HRA DV3 65 113...
Page 66: ...DC Inverter Air 2 2TCA 18HRA DVO TC A 24HRA DVO 66 113...
Page 82: ...DC Inverter Air 82 113...