DC Inverter Air
2)
The configuration of air conduit joint on the site may not reduce its effective cross section;
3)
The support and hanger of air conduit cannot be set up at air port, valve, manhole and automatic
control mechanism; the boom/suspender shall not be directly fixed on the flange;
4)
The configuration of air conduit joint on the site may not reduce its effective cross section;
5)
Deviation standard for hoisting operation of air conduit
Horizontal Installation
Vertical Installation
Open‐type Installation
δ≤3mm/m Δ≤20mm
δ≤2mm/m Δ≤20mm
Concealed Installation
Correct position, free from any obvious deviation
δ— Deviation per meter;
— total deviation
6)
The support and hanger of heat‐preservation air conduit shall be located outside of the insulation
layer, and may not damage the insulation layer;
7)
The spacing of support and hanger shall comply the following provisions unless otherwise required
in the design:
Diameter(long side) size<400mm
Diameter(long side)≥ 400mm
Horizontal spacing
≤4mm
≤3mm
Vertical spacing
≤4mm, each riser shall be equipped with less than 2 fixed parts
6) Installation of Drain Pipes
Warning:
Must install drainpipes according to the following figure, avoiding generating condensed water and leakage
water.
a. Assemble the main body according to the Figure.
b. The opening of drainpipes can be installed on the leftside or the right side . Could remove the drain stopper
and put it on the leftside or the right side.
c. For the best effect, should keep pipes as short as possible. Tilt the pipes to ensure the flow of fluid.
d. Make sure the drainpipes have admirable heat insulation.
e. It is necessary to install a trap near the opening of the drainpipe, so that when the machine is working, the
pressure in the inside of the machine is lower than atmospheric pressure. If there isn't an elbow, the water will
splash and the pipe will produce a bad smell.
f. keep straightness of drainpipes so as to remove dirt.
g. Seal the drainpipe on the other side of the machine, then wrap up the drainpipe in the heat‐barrier materials.
h. Put water into the drain pan to test whether the water can be discharged swimmingly.
i. In humid conditions , please must use a add‐on drain pan(commercially available) to cover the whole area of
the indoor unit.
35
/
113
Summary of Contents for ITCA-60CHRA/DV3I
Page 1: ...Technical Manual for DC Inverter Air Conditioner 1 113...
Page 13: ...DC Inverter Air 1 4 Electrical Wiring Diagram 13 113...
Page 14: ...DC Inverter Air 1 5 Air Velocity and Temperature Distributions Airflow velocity 14 113...
Page 22: ...DC Inverter Air 22 113...
Page 28: ...DC Inverter Air 2 3 Service Space 2 4 Wiring Diagrams 28 113...
Page 41: ...DC Inverter Air 3 2 Wirin g Diagra ms 41 113...
Page 42: ...DC Inverter Air A irflow velo city Discharge angle 60 FLOOR 42 113...
Page 43: ...DC Inverter Air Airflow velocity Temperature 43 113...
Page 64: ...DC Inverter Air 7 2 Electrical Wiring Diagram 2 1 TCA 36HRA DV 64 113...
Page 65: ...DC Inverter Air 2 2 TCA 48H RA DV3 TCA 60HRA DV3 65 113...
Page 66: ...DC Inverter Air 2 2TCA 18HRA DVO TC A 24HRA DVO 66 113...
Page 82: ...DC Inverter Air 82 113...