DC Inverter Air
2)
Th e attention shall be paid to the assembly direction and angle of the liquid pipe and gas pipe openings
to avoid the oil backflow or accumulation;
3)
The alternative method for nitrogen injection is the standard operation method during the welding
operation.
A.
Preparation for fire prevention (to avoid the fire, conduct in clean area, prepare the fire‐fighting
equipment and water for emergency purpose);
B.
Pay attention to the avoidance of scalds;
C.
Pay attention to the gap between pipe and nipples (avoid the leakage);
D.
Confirm the support strength for pipes.
The spacing criteria for supports of horizont al pipes (cop er tube) are as follows:
Cr iteria(mm)
Below 20
25‐40
50
Max. spacing(m)
1. 0
1.5
2.9
Minimum embedding depth and gap of copp er tube nipples/fittings
Unit mm
Type
Outer
Minimum
Gap A‐D
embedding
diame ter D
depth B
5
<
D
<
8
6
0.05‐0.21
8
<
D
<
12
7
11
<
D
<
16
8
0.05‐0.27
16
<
D
<
25
10
25
<
D
<
35
12
0.05‐0.35
35
<
D
<
45
14
4.
Flare Connection
1)
Th e auxiliary connecting pipe must be annealed before the flaring operation;
2)
The pipe shall be cut by pipe cutter (the large diameter pipe shall use the large cutter; when the diameter is
so large that it cannot be cut by the pipe cutter, the metal saw shall be used, but attention
71
/
113
Summary of Contents for ITCA-60CHRA/DV3I
Page 1: ...Technical Manual for DC Inverter Air Conditioner 1 113...
Page 13: ...DC Inverter Air 1 4 Electrical Wiring Diagram 13 113...
Page 14: ...DC Inverter Air 1 5 Air Velocity and Temperature Distributions Airflow velocity 14 113...
Page 22: ...DC Inverter Air 22 113...
Page 28: ...DC Inverter Air 2 3 Service Space 2 4 Wiring Diagrams 28 113...
Page 41: ...DC Inverter Air 3 2 Wirin g Diagra ms 41 113...
Page 42: ...DC Inverter Air A irflow velo city Discharge angle 60 FLOOR 42 113...
Page 43: ...DC Inverter Air Airflow velocity Temperature 43 113...
Page 64: ...DC Inverter Air 7 2 Electrical Wiring Diagram 2 1 TCA 36HRA DV 64 113...
Page 65: ...DC Inverter Air 2 2 TCA 48H RA DV3 TCA 60HRA DV3 65 113...
Page 66: ...DC Inverter Air 2 2TCA 18HRA DVO TC A 24HRA DVO 66 113...
Page 82: ...DC Inverter Air 82 113...