Twin City Installation and Maintenance Manual IM-3100

3

Motors  require  no  lubrication  for  10  years  of  normal 

operation.
The  inlet  venturi  is  molded  shock-resistant,  bonded, 

reinforced fiberglass and will require no maintenance.

Wall Application

1. Servicing or inspecting the unit can be accomplished 

from  the  exterior  by  removing  the  flanged  extruded 

louver  and  from  the  interior  of  the  building  by 

removing the fiberglass inlet (see Figure 2).

2. To remove the  motor  assembly for servicing, unplug 

the motor from the provided outlet and unfasten the 

four  vibro-isolator  bolts.  The  entire  motor  assembly, 

including the wheel and bearing (belt drive units), will 

slide out of the housing.

Inline Application

For easy maintenance of the inlet unit, provide a dropout 

section  between  the  ductwork  and  duct  adapter  (see 

Figure 3).
Servicing  or  inspection  can  then  be  accomplished  by 

removing  the  dropout  section,  then  removing  the 

fiberglass  inlet.  The  motor  assembly  can  then  be 

removed by disconnecting the motor from the provided 

outlet  and  unfastening  the  four  vibro-isolator  bolts. 

Periodic  inspection  and  cleaning  of  the  fan  will  insure 

smooth operation.

Figure 1. Removal of Wood Shipping Supports

Housing

Instructions: Remove wood shipping supports 

frame before installing unit

.

Figure 2. Wall Application

Electrical Wiring By Others

Hole Provided for Electrical Entrance Into Unit

Electrical Junction Box With Outlet

Belt Drive Motor 

Assembly

Direct Drive Motor 

Assembly

Louver

Assembly

Fiberglass Inlet Venturi

Trim Angle Assembly

Fan 

Housing

Assembly

Access To Power Pack of Ventilator

By Removing 4 Fasteners (Interior Side) 

or Louvers (Exterior Side)

Summary of Contents for 14HA1B

Page 1: ...he electrical wiring into the unit 3 Anchor the box in the wall keeping a minimum of 23 8 between the outside wall and any part of the box or the power assembly 4 Fasten the flanged extruded louver to the exterior wall Inline Application 1 Remove wood shipping supports from fan assembly see Figure 1 2 Attach duct adapter and companion angles to unit per Figure 3 with fasteners supplied 3 Before an...

Page 2: ...le 2 Maximum Fan RPM Belt Driven Units MODEL HAB MOTOR HP MAXIMUM FAN RPM 12HA1B 2B 3B 1 4 1738 14HA1B 2B 3B 1 4 1468 14HA4B 1 3 1615 14HA5B 1 2 1849 18HA1B 2B 1 4 945 18HA3B 1 3 1040 18HA4B 1 2 1191 18HA5B 3 4 1363 24HA1B 1 4 575 24HA2B 1 3 633 24HA3B 1 2 725 24HA4B 3 4 830 24HA5B 1 913 30HA1B 1 3 436 30HA2B 1 2 500 30HA3B 3 4 572 30HA4B 1 630 30HA5B 11 2 721 30HA5B 2 793 Maintenance General Fan ...

Page 3: ...of the inlet unit provide a dropout section between the ductwork and duct adapter see Figure 3 Servicing or inspection can then be accomplished by removing the dropout section then removing the fiberglass inlet The motor assembly can then be removed by disconnecting the motor from the provided outlet and unfastening the four vibro isolator bolts Periodic inspection and cleaning of the fan will ins...

Page 4: ...mbly on Exterior Wall Wiring By Others Duct Adaptor Shipped Loose With Fasteners Access to Power Pack of Inline Unit By Removing 4 Fasteners Dropout Section of Duct For Easy Maintenance By Others Companion Angles Shipped Loose With Fasteners Ductwork By Others Figure 3 Inline Application ...

Page 5: ...TORY OR OTHERWISE INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE In no event shall seller be liable to buyer for indirect incidental collateral or consequential damages of any kind BUYER S FAILURE TO PAY THE FULL AMOUNT DUE WITHIN SIXTY 60 DAYS OF DATE OF INVOICE SHALL OPERATE TO RELEASE SELLER FROM ANY AND ALL LIABILITY OR OBLIGATION ARISING PURSUANT TO ANY ...

Page 6: ...TWIN CITY FAN BLOWER WWW TCF COM 5959 Trenton Lane N Minneapolis MN 55442 Phone 763 551 7600 Fax 763 551 7601 ...

Reviews: