background image

2

Twin City Installation and Maintenance Manual IM-3100

Check, Test & Start Procedure

1. Check to verify that the wheel is free to rotate.
2. Verify that supply voltage on the line side of disconnect 

agrees with voltage on unit identification plate and is 

within the utilization voltage range as indicated in Table 

1.

3. On  three-phase  units  check  and  calculate  phase 

unbalance as follows:

  % Voltage Unbalance = 100 x max. voltage deviation         

    

       from avg. voltage ÷ avg. voltage

  Given example: With voltage of 220, 216 and 213
  How To Use The Formula:

  a. Avg. Voltage = 220 + 216 + 213 = 649 ÷ 3 = 

216

  b. Max. Voltage Deviation From Avg. Voltage =

220 – 216 = 4

  c. % Voltage Unbalance = 100 x (4 ÷ 216) = 1.8%

  Voltage unbalance should not exceed 2%.

4. Apply power to unit and check rotation of wheel with 

the directional arrow on the unit.

 

Table 1. Utilization Voltages

SYSTEM VOLTAGE/ 

UNIT NAMEPLATE

UTILIZATION VOLTAGE

MIN.

MAX.

115/60/1

104

127

208-230/60/1 or 208- 230/60/3

187

253

230/60/1 or 230/60/3

207

253

277/60/1

249

305

200/60/3

180

220

380/60/3

342

418

460/60/3

414

506

575/60/3

517

633

110/50/1

99

121

220/50/1

198

242

380-415/50/3

342

456

440/50/3

396

484

Electric shock hazard. Could cause severe injury or 

death. Failure to bond the frame of this equipment to 

the building electrical ground by use of the grounding 

terminal  provided  or  other  acceptable  means  may 

result in electrical shock. Disconnect electric power 

before servicing equipment. Service to be performed 

only by qualified personnel.

WARNING

5. 

Electrical Input Check: Perform check of fan ampere 

draw  and  verify  that  motor  nameplate  amps  are  not 

exceeded. Take account of the service factory range 

if motor is nameplated above a 1.0 service factor.

6. 

Fan RPM Check:  Fan  RPM  should  be  checked  and 

verified  with  a  tachometer.  Refer  to  Table  2  for 

maximum fan RPM values.

Table 2. Maximum Fan RPM (Belt Driven Units)

MODEL

HAB

MOTOR

HP

MAXIMUM

FAN RPM

12HA1B, 2B, 3B

1/4

1738

14HA1B, 2B, 3B

1/4

1468

14HA4B

1/3

1615

14HA5B

1/2

1849

18HA1B, 2B

1/4

945

18HA3B

1/3

1040

18HA4B

1/2

1191

18HA5B

3/4

1363

24HA1B

1/4

575

24HA2B

1/3

633

24HA3B

1/2

725

24HA4B

3/4

830

24HA5B

1

913

30HA1B

1/3

436

30HA2B

1/2

500

30HA3B

3/4

572

30HA4B

1

630

30HA5B

1

1

/

2

721

30HA5B

2

793

Maintenance

General

Fan  shaft  bearings  on  belt  drive  units  are  factory 

lubricated  and  require  no  lubrication  for  the  first  3-6 

months  of  operation.  Lubricate  at  intervals  shown  in 

Table  3  thereafter.  With  fan  running  and  with  a  low 

pressure  grease  gun,  add  grease  slowly  until  a  slight 

bead  forms  between  the  seals.  Use  Sinclair  Litholene, 

Shell Gadus S2 V100 2, Socony Vacuum Armvac 781, 

Sinclair Oil Stranolith 57 or equal.

Belts on belt-drive units should be readjusted after 24 

hours of operation. Loosen motor base bolts and apply 

15  lbs.  pull  per  belt  for  proper  belt  tensions.  Tighten 

motor base bolts.
Check  contact  surfaces  of  belt  for  excessive  wear.  If 

belts have a slick, glazed look or are cracked, belts are 

slipping. Replace belts as required.

OPERATING CONDITION

GREASING INTERVAL

FAIRLY CLEAN

6 to 12 Months

MODERATE TO

EXTREMELY DIRTY

1 Month

Table 3.  Bearing Lubrication Interval

 

(Belt Drive Model HAB Only)

1. 

Frequency  or  regreasing  will  vary,  depending  on  the  hours  of 

operation, temperature and surrounding conditions.

2. 

Bearings  have  been  prelubricated  from  factory  with  NLGI  Grade 

No. 2 lithium-12 hydroxysterate base grease.

Especially  check  three-phase  units  for  rotation. 

For  three-phase,  rotation  can  be  changed  by 

interchanging any two of the three line leads. If the 

unit is checked on temporary wiring, it should be 

rechecked  when  permanently  installed.  Motor 

burn-out  or  tripped  overload  protection  devices 

are usually the result of wrong rotation.

WARNING

Running fan at an RPM greater than the maximum 

RPM value in Table 2 will overload the fan motor 

and lead to premature motor failure.

WARNING

Summary of Contents for 14HA1B

Page 1: ...he electrical wiring into the unit 3 Anchor the box in the wall keeping a minimum of 23 8 between the outside wall and any part of the box or the power assembly 4 Fasten the flanged extruded louver to the exterior wall Inline Application 1 Remove wood shipping supports from fan assembly see Figure 1 2 Attach duct adapter and companion angles to unit per Figure 3 with fasteners supplied 3 Before an...

Page 2: ...le 2 Maximum Fan RPM Belt Driven Units MODEL HAB MOTOR HP MAXIMUM FAN RPM 12HA1B 2B 3B 1 4 1738 14HA1B 2B 3B 1 4 1468 14HA4B 1 3 1615 14HA5B 1 2 1849 18HA1B 2B 1 4 945 18HA3B 1 3 1040 18HA4B 1 2 1191 18HA5B 3 4 1363 24HA1B 1 4 575 24HA2B 1 3 633 24HA3B 1 2 725 24HA4B 3 4 830 24HA5B 1 913 30HA1B 1 3 436 30HA2B 1 2 500 30HA3B 3 4 572 30HA4B 1 630 30HA5B 11 2 721 30HA5B 2 793 Maintenance General Fan ...

Page 3: ...of the inlet unit provide a dropout section between the ductwork and duct adapter see Figure 3 Servicing or inspection can then be accomplished by removing the dropout section then removing the fiberglass inlet The motor assembly can then be removed by disconnecting the motor from the provided outlet and unfastening the four vibro isolator bolts Periodic inspection and cleaning of the fan will ins...

Page 4: ...mbly on Exterior Wall Wiring By Others Duct Adaptor Shipped Loose With Fasteners Access to Power Pack of Inline Unit By Removing 4 Fasteners Dropout Section of Duct For Easy Maintenance By Others Companion Angles Shipped Loose With Fasteners Ductwork By Others Figure 3 Inline Application ...

Page 5: ...TORY OR OTHERWISE INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE In no event shall seller be liable to buyer for indirect incidental collateral or consequential damages of any kind BUYER S FAILURE TO PAY THE FULL AMOUNT DUE WITHIN SIXTY 60 DAYS OF DATE OF INVOICE SHALL OPERATE TO RELEASE SELLER FROM ANY AND ALL LIABILITY OR OBLIGATION ARISING PURSUANT TO ANY ...

Page 6: ...TWIN CITY FAN BLOWER WWW TCF COM 5959 Trenton Lane N Minneapolis MN 55442 Phone 763 551 7600 Fax 763 551 7601 ...

Reviews: