background image

TC1720

 (Optional Dual Optics)

User's Manual

Rev. 1.4

-10-

Chapter 3 - Troubleshooting

General

Typically, most problems encountered during installation are related to an improperly wired RS-442/449 cable
or a break in the integrity of the fiber optic link (cable or connectors).

All LEDs are "Off"

If no LEDs are lit on the unit, check the DC power supply, terminal block connector plug, and/or power
source.  If the problem persists, contact the Technical Support Department at TC Communications, Inc.

Alarm LED

When there is an alarm condition, the red "ALARM" LED will be lit and the "RxA" LED will also flash to
indicate the optic signal has been lost.  The Alarm will also trigger the dry contact relay switch.

Optic Cable Types

Conventionally, fiber optic cable with yellow-colored insulation is used for single mode applications; gray or
orange-colored insulated cable is for multimode use.  If multimode cable is used in a single mode application,
the test results could be erroneous and confusing.

Calculating the Loss on the Fiber

The fiber optic link and/or the connectors are frequently the source of communication problems.  If problems
are present, check the optic connectors and the integrity of the link first.  Ideally, the link should be calibrated
for total loss after the installation has been completed.  This will accomplish two things: (1) it will verify that
the total loss of the link is within the loss budget of the device and (2) it will provide a benchmark for future
testing.  For example, a system that has been tested as having 6dB of signal loss when installed should not
suddenly test out as having a loss of 10dB.  If this were the case, however, the fiber link or connector would
probably be the source of the problem.

These are the reference values we use to calculate the loss on the fiber:

Multimode 1310nm

:

2 dB loss per km on 62.5/125µm cable*

Single Mode 1310nm

:

0.5 dB loss per km on 9/125µm cable*

Single Mode 1550nm

:

0.25 dB loss per km on 9/125µm cable*

*These numbers are listed for reference only.  We recommend an OTDR reading be used to measure actual link loss.

RS-442/449 Cable Verification

1.

Make sure the electrical signal connections match the pin assignments for the device (refer to page 3
for DCE/DTE pin connections). Verify signal connections by checking the status LEDs on the front panel
of the TC1720.  Verify that the pin signal connections match the appropriate LED responses (see Figures
1, 2 & 3).

2.

Be sure that all switches are set correctly. All the front panel DIP switches should be in up (off) position.
All the "SW1 Internal DIP Switches"  are generally factory configured. However, the clock settings can
be user configured with SW1-5, SW1-6, SW1-7, and SW1-8, to suit  the user's timing needs, refer to table
1 on page 5.

Important Warranty Note:

If the need arises for any internal configuration, please contact the Technical Support Department at TC
Communications, Inc @ (949) 852-1973. Warranty voided if product seal is broken.

Summary of Contents for TC1720

Page 1: ...fica tion TC Communications Inc reserves the right to change or modify the contents of this manual at any time without prior notification TC1720 RS 422 RS 449 Async Sync FIBER OPTIC MODEM with Optiona...

Page 2: ...uipment Location 8 Installation Procedure Summary 8 Typical Point to Point Application Diagram 9 Chapter 3 Troubleshooting 10 General 10 All LEDs are Off 10 Alarm LED 10 Optic Cable Types 10 Calculati...

Page 3: ...449 Async Sync Data Rates Async Up to 10 Mbps Sync Up to 5 Mbps Connector DB37 Male DCE DTE switch selectable Virtual Pin Assignments Theory of Operation Figure 1 Connecting a DTE to DCE Device Logic...

Page 4: ...signal lost RxB Solidly lit optic received OK from secondary side B side Flashing when optic signal lost or B side is not enabled USE B Solidly lit when secondary optic signal is being used due to pr...

Page 5: ...t alarm These functions can be initiated from one of four DIP switches accessible from front panel Under normal operation all the switches should be set in UP position SW1 Internal PCB Dip Switches Th...

Page 6: ...ivity and distance are listed for reference only These numbers may vary RS 422 449 Termination Resistor A termination resistor is usually necessary for RS 422 applications Without proper termination t...

Page 7: ...ill force the switch to a CLOSED position This relay can be used in conjunction with an external device to signal an alarm condition Power Supply and Rear Panel The TC1720 consumes very low power The...

Page 8: ...e all DIP switches are in the up Off position and double check the polarity at the DC power s terminal block connector The installation procedure is as follows 1 Connect your DTE DCE Device to the DB3...

Page 9: ...ntegrity of the system and provide a benchmark for future troubleshooting efforts see Chapter 3 Troubleshooting Figure 5 Typical Point to Point RS 442 449 Application Diagram DTE DEVICE Dual Optic Mod...

Page 10: ...f the link is within the loss budget of the device and 2 it will provide a benchmark for future testing For example a system that has been tested as having 6dB of signal loss when installed should not...

Page 11: ...x A LED on the front panel being solidly lit This indicates that the receiving cable is correctly connected to the remote unit s optic TxA On Dual Optics Models the same applies to RxB and TxB Dual Op...

Page 12: ...nnectors ST or FC Pre Installation Tests 1 Make sure the appropriate power supply accompanies the TC1720 unit see page 7 2 To verify that the unit functions properly plug in only the power connector t...

Page 13: ...Now turn the front panel SW2 2 LOCLB dip switch to the down On position to enable the Local Loopback test function 8 At this point the tester should indicate a Synchronous signal being received indica...

Page 14: ...gh 128Kbps Synchronous 5 The data bits should be selected as 8 bits and the data pattern should be set to 2047 on the BERT tester 6 At this point the tester should indicate a Synchronous signal being...

Page 15: ...nd connectors are good and the cable has been connected properly 7 Verify the following LEDs on both the Local and Remote TC1720 units On the Local unit the TxD RxD TxClk RxClk RxA PWRA or PWRB and Vc...

Page 16: ...een connected properly 6 Verify that the TxD RxD TxClk RxClk RxA PWRA or PWRB and Vcc LEDs are solidly lit on both the Local and Remote TC1720s Note the ALARM LED will be Off since there are optical f...

Page 17: ...ding SW1 1 switch 1 of the SW1 Internal DIP Switch to the right on position 2a For Sync units SW1 4 disabled Off Turn on the RMTLB by pressing down the DIP switches 1 of Front Panel DIP Switches on th...

Page 18: ...Optic RxA DRY CONTACT ALARM SW1 1 2 3 4 5 6 7 8 ON SW1 Internal DIP Switches Used to configure TC1720 to enable the signal generator test to change DCE Off or DTE On device to enable secondary optic...

Page 19: ...er Indicators System status ALARM PWR A PWR B Vcc Rx A Rx B USE B DTE Electrical Signal Status RxD TxD Optic Signal Status TxA RxB for Dual Optics TxB and RxB Power Source Standard 12VDC 500mA typical...

Page 20: ...tion may first inspect such goods at the premises of the Buyer or may give written authorization to Buyer to return the goods to TC Communications Inc transportation charges prepaid for examination by...

Reviews: