25
A03
Auto-sync current (will only show when A01 is set to LEGACY). When the charge current is
below this percentage of the battery capacity (see Function F1.1), the battery will be
considered as fully charged. Make sure that this value is always slightly greater than the
current at which the charger maintains the battery or stops charging.
Default: 2.0%
Range: 0.5 - 10.0%
Step size: 0.1%
A04
Auto-sync time (will only show when A01 is set to LEGACY). This is the time that both
Auto-sync parameters A02 and A03 must be met in order to consider the battery as fully
charged.
Default: 240sec
Range: 0
–
3600sec
Step size: variable
A05
Auto-sync sensitivity (will only show when A01 is set to LEGACY). Only change this setting
when A02, A03 and A04 are set correctly and automatic synchronization still fails. If
automatic synchronization takes too long or does never occur, lower this value. When the
battery monitor synchronizes too early, increase this value.
Default: 5
Range: 0
–
10
Step size: 1
A07
Bank 1 series cell count. Allows you to edit the number of internal series cells of your used
batteries that was automatically determined after completing the Setup Wizard. See table
2 in chapter 2.2 for more information.
Default: dynamic
Range: 2
–
30
Step size: 1
A08
Bank 2 series cell count (will only show when F2.0 is set to AUX.BAT). Allows you to edit
the number of internal cells of your used batteries, that was automatically determined
after completing the Setup Wizard. See table 2 in chapter 2.2 for more information.
Default: dynamic
Range: 2
–
30
Step size: 1
A09
Bank 3 series cell count (will only show when F3.0 is set to AUX.BAT). Allows you to edit
the number of internal cells of your used batteries, that was automatically determined
after completing the Setup Wizard. See table 2 in chapter 2.2 for more information.
Default: dynamic
Range: 2
–
30
Step size: 1
A12
Temperature averaging filter. Specifies the noise filter setting at the temperature sensor
input. The default value of 1 will be fine for most applications. Only in case of long
temperature sensor cables and/or environments with extremely high RF interference
levels, it is advised to set this value to 2.
Default: 1
Range: 0
–
2
Step size: 1
All changed Function settin
gs remain in the Expert Modular’
s internal memory. Even when
the supply voltage has been interrupted. This also applies to the stored Status and History
items.
Summary of Contents for Expert Modular
Page 2: ...2...
Page 4: ...4 English Page 5 Nederlands Pagina 32 Deutsch Seite 59 Francais Page 88 Espa ol P gina 117...
Page 5: ...5 Owner s manual...
Page 35: ...35 Gebruiksaanwijzing...
Page 65: ...65 Bedienerhandbuch...
Page 97: ...97 Mode d emploi...
Page 129: ...129 Manual del propietario...