11. The capability of this terminal to read the
thermistor probe can be checked by the
following method:
a. Remove the thermistor probe wire from the
"MIX 1" terminal.
b. Connect the "MIX 1" terminal directly to
ground (simulating a warm probe). The MIX
light will illuminate.
c. Remove the terminal connection from
ground (simulating a cold probe). The
PUMP light will illuminate.
If the lights do not react, the panel is defective.
12. Press the MIX keypad once.
13. The MIX OUT light is lit, indicating that the control
is now reading the BARREL (freezing cylinder)
probe terminal.
14. Check the freezing cylinder probe (as in
Step 13) by removing the wire from the panel.
15. Press the MIX keypad again, and the self-test
program is terminated.
Summary of Contents for Freezemaster 336
Page 23: ...Control Overview...
Page 31: ...Model 336 Exploded View...
Page 33: ...Model 336 Panel Identification...
Page 35: ...Model 338 Exploded View...
Page 37: ...Model 338 Panel Identification...
Page 39: ...Model 339 Exploded View...
Page 41: ...Model 339 Panel Identification...
Page 43: ...Model 750 Exploded View...
Page 45: ...Model 750 Panel Identification...
Page 47: ...Model 751 Exploded View...
Page 49: ...Model 751 Panel Identification...
Page 51: ...Model 754 Exploded View...
Page 53: ...Model 754 Panel Identification...
Page 55: ...Model 774 Exploded View...
Page 58: ...Model 774 Panel Identification...
Page 60: ...Model 794 Exploded View...
Page 62: ...Model 794 Panel Identification...
Page 66: ...Control A X32963 27A Models 339 754 208 230 60 1...
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......