51
Frequency measured from Source
– side
13
, Hz
F-
40-60 at 50Hz
40-70 at 60Hz
0.01 Hz
Single-phase power factor
PFa, PFb, PFc
-1
… 1
0.01
Three-phase power factor
PF3ph
-1
… 1
0.01
Phase-to-earth voltages measured from side, kV
Ua+, Ub+, Uc+
0 … 30
0.1 kV
Phase-to-earth voltages measured from Source - side, kV
Ua-, Ub-, Uc-
0 … 30
0.1 kV
Phase-to-phase voltages measured from side, kV
Uab+, Ubc+, Uac+
0 … 30
0.1 kV
Phase-to-phase voltages measured from Source - side, kV
Uab-, Ubc-, Uac-
0
… 30
0.1 kV
Positive sequence active power, kW
P1
-65535
…
65535
1 kW
Single-phase active power, kW
Pa, Pb, Pc
-
65535 …
65535
1 kW
Three-phase active power, kW
P3ph
-
65535 …
65535
1 kW
Single-phase reactive power, kVAr
Qa, Qb, Qc
-
65535 …
65535
1 kVAr
Three-phase reactive power, kVAr
Q3ph
-
65535 …
65535
1 kVAr
Single-phase active energy, kWh
Wa, Wb, Wc
0 … 9999999
1 kWh
Three-phase active energy, kWh
W3ph
0 … 9999999
1 kWh
Single-phase reactive energy, kVArh
Ea, Eb, Ec
0 … 9999999
1 kVArh
Three-phase reactive energy, kVArh
E3ph
0 … 9999999
1 kVArh
Phase angle difference between U1+ and U1-, degrees
PhAngDifU1
0 … 180 or
“Undefined”
1 degree
Angle between Un and In, degrees
An
-
179 … 180 or
“Undefined”
1 degree
Signal filtering effectively rejects higher harmonics. Phase current measuring channels are additionally
equipped with inrush filters.
Inrush Filter
Reclosers described in the current product guide incorporate a unique inrush filter. This allows filtering of
magnetizing currents occurring at energizing transformers or distribution feeders with step-down-transformers.
In contrast to the widely used inrush restraint, which blocks the operation of protection for the period of inrush,
the filter leaves all protection active and sensitive to faults for the whole period of line energizing.
The advantages are:
•
This feature makes it possible to select the settings of current-based protection elements based on actual
load and fault levels, not considering any side effects due to transformer load energizing;
•
If, after maintenance closing or performing backfeed restoration for a faulty feeder part, the fault clearing
time is significantly reduced as all protection elements operate correctly without any delays.
Figure 26 and Figure 27 demonstrate the comparison of current measurement results at load energizing
captured by the recloser without and with inrush filter enabled.
Figure 26
Basic frequency phase currents RMS. No inrush filter applied
Summary of Contents for Rec15
Page 1: ......
Page 5: ...1 Introduction...
Page 9: ...2 Technical Parameters...
Page 14: ...3 Product Description...
Page 26: ...26 Figure 25 Anti vandal housing...
Page 27: ...4 Functionality...
Page 56: ...5 Product Handling...
Page 69: ...6 Installation...
Page 81: ...7 Commissioning...
Page 84: ...8 Operation...
Page 99: ...99 Figure 76 Settings uploading wizard...
Page 100: ...9 Maintenance and Troubleshooting...
Page 114: ...114 Figure 90 Securing the trip hook shaft against rotation...
Page 115: ...10 Product Coding...
Page 122: ...11 Appendices...
Page 128: ...128 Appendix 4 Recloser Control Drawings Figure 99 Dimensions of RC5_4...
Page 133: ...133 Figure 106 Dimensions of standard OSM mounting kit arrangement for lateral installation...
Page 134: ...134 Figure 107 Dimensions of interface bracket...
Page 135: ...135 Figure 108 Dimensions of OSM mounting kit with M16 pole interface front installation...
Page 136: ...136 Figure 109 Dimensions of OSM mounting kit with M16 pole interface lateral installation...
Page 137: ...137 Figure 110 Dimensions of OSM mounting kit with M20 pole interface front installation...
Page 138: ...138 Figure 111 Dimensions of OSM mounting kit with M20 pole interface lateral installation...
Page 149: ...149 Figure 122 Dimensions of OSM substation mounting kit...
Page 152: ...152 Figure 125 Dimensions of RC mounting kit for through the pole installation...
Page 153: ...153 Figure 126 Dimensions of RC substation mounting kit...
Page 154: ...154 Figure 127 Dimensions of VT mounting kit One VT holder...
Page 163: ...163 Appendix 8 Connectors Drawings Figure 141 Dimensions of aerial connector...
Page 164: ...164 Figure 142 Dimensions of bird guards for aerial connector...
Page 165: ...165 Figure 143 Dimensions of two hole NEMA connector...
Page 166: ...166 Figure 144 Dimensions of bird guards for two hole NEMA connector...
Page 167: ...167 Figure 145 Dimensions of four hole NEMA connector...
Page 168: ...168 Figure 146 Dimensions of bird guards for four hole NEMA connector...
Page 169: ...169 Figure 147 Dimensions of Burndy NEMA connector...
Page 170: ...170 Appendix 9 Recloser Control Wiring Diagram Figure 148 RC5_4 wiring diagram...
Page 172: ......