35
measured current does not exceed the pickup setting and the Reset timer stops counting, a current reclosing
cycle will be continued. In the case that, after closing, the measured current does not exceed the pickup setting
within the Reset time period, a new autoreclosing sequence will be enabled and will be executed for
consequent faults. The Reset time counter starts counting from zero for each automatic closing event in an
autoreclosing sequence.
First closure time (SST timer)
The Single shot to lockout algorithm is supported by the AR OC element. This function allows tripping and
lockout (preventing autoreclosing) if a fault has been detected by the operator during the First closure time.
The Single shot to lockout function will be disabled in case “Unconditional AR” is selected for First closure
mode. Recloser can make up to 4 closing operations including the first close initiated by operator.
Overcurrent Interruption Detection (OCID)
This element is available for OCR mode “Sectionalizer” only.
This element provides detection of the overload, phase-to-phase and three phase short circuit fault passage
and interruption due to operation of upstream device. OCID operates according to definite time TCC.
OCID settings are described in Table 27 and Table 28.
Table 27
– Radial line recloser OCID element settings
Settings
Designation
Range
Step size
Default
Operating mode
Mode
Enable/Disable
n.a.
Enable
Detection time, s
Td
0.00
–100.00
0.01
0.1
Pickup current, A
Ip
10
–6000
1
100
Reset time, s
Tres
0.00
–100.00
0.01
0.1
Fault interruption reset time, s
Tfir
0.10
–100.00
0.01
1.00
Table 28
– Ring line recloser OCID element settings
Settings
Designation
Range
Step size
Default
Operating mode+
Mode+
Enable/Disable
n.a.
Enable
Detection time+, s
Td+
0.00
–100.00
0.01
0.1
Pickup , A
Ip+
10
–6000
1
100
Reset time+, s
Tres+
0.00
–100.00
0.01
0.1
Fault interruption reset time+, s
Tfir+
0.10
–100.00
0.01
1.00
Operating mode-
Mode-
Enable/Disable
n.a.
Enable
Detection time-, s
Td-
0.00
–100.00
0.01
0.1
Pickup current-, A
Ip-
10
–6000
1
100
Reset time-, s
Tres-
0.00
–100.00
0.01
0.1
Fault interruption reset time-, s
Tfir-
0.10
–100.00
0.01
1.00
Earth Fault Interruption Detection (EFID)
This element is available for OCR mode “Sectionalizer” only.
This element provides detection of the earth fault current passage and interruption due to operation of
upstream device. EFID operates according to definite time TCC.
EFID settings are described in Table 29 and Table 30.
Table 29
– Radial line recloser EFID element settings
Settings
Designation
Range
Step size
Default
Operating mode
Mode
Enable/Disable
n.a.
Enable
Detection time, s
Td
0.00
–100.00
0.01
0.1
Pickup current, A
Ip
5
–6000
1
100
Reset time, s
Tres
0.00
–100.00
0.01
0.1
Fault interruption reset time, s
Tfir
0.10
–100.00
0.01
1.00
Summary of Contents for Rec15
Page 1: ......
Page 5: ...1 Introduction...
Page 9: ...2 Technical Parameters...
Page 14: ...3 Product Description...
Page 26: ...26 Figure 25 Anti vandal housing...
Page 27: ...4 Functionality...
Page 56: ...5 Product Handling...
Page 69: ...6 Installation...
Page 81: ...7 Commissioning...
Page 84: ...8 Operation...
Page 99: ...99 Figure 76 Settings uploading wizard...
Page 100: ...9 Maintenance and Troubleshooting...
Page 114: ...114 Figure 90 Securing the trip hook shaft against rotation...
Page 115: ...10 Product Coding...
Page 122: ...11 Appendices...
Page 128: ...128 Appendix 4 Recloser Control Drawings Figure 99 Dimensions of RC5_4...
Page 133: ...133 Figure 106 Dimensions of standard OSM mounting kit arrangement for lateral installation...
Page 134: ...134 Figure 107 Dimensions of interface bracket...
Page 135: ...135 Figure 108 Dimensions of OSM mounting kit with M16 pole interface front installation...
Page 136: ...136 Figure 109 Dimensions of OSM mounting kit with M16 pole interface lateral installation...
Page 137: ...137 Figure 110 Dimensions of OSM mounting kit with M20 pole interface front installation...
Page 138: ...138 Figure 111 Dimensions of OSM mounting kit with M20 pole interface lateral installation...
Page 149: ...149 Figure 122 Dimensions of OSM substation mounting kit...
Page 152: ...152 Figure 125 Dimensions of RC mounting kit for through the pole installation...
Page 153: ...153 Figure 126 Dimensions of RC substation mounting kit...
Page 154: ...154 Figure 127 Dimensions of VT mounting kit One VT holder...
Page 163: ...163 Appendix 8 Connectors Drawings Figure 141 Dimensions of aerial connector...
Page 164: ...164 Figure 142 Dimensions of bird guards for aerial connector...
Page 165: ...165 Figure 143 Dimensions of two hole NEMA connector...
Page 166: ...166 Figure 144 Dimensions of bird guards for two hole NEMA connector...
Page 167: ...167 Figure 145 Dimensions of four hole NEMA connector...
Page 168: ...168 Figure 146 Dimensions of bird guards for four hole NEMA connector...
Page 169: ...169 Figure 147 Dimensions of Burndy NEMA connector...
Page 170: ...170 Appendix 9 Recloser Control Wiring Diagram Figure 148 RC5_4 wiring diagram...
Page 172: ......