Once the travel setup is complete, the door must be closed and LED DL1 must flash green.
SENSOR TEST SETTING
• Use only sensors which feature testing wires, connecting these to the wire terminals 11 and 12
of the controller DC19;
• Set DIP #11 and #12 on SW1 to ON in order to enable the test
;
• Test will be performed at the beginning of each cycle (except when reversing motion)
.
LOGIC ADJUSTMENTS
Trimmer
Function
Description
TM1
OPENING
SPEED
Adjusts Opening Speed.
TM2
CLOSING
SPEED
Adjusts Closing Speed.
TM3
OPENING
TORQUE
Adjusts Opening Torque.
TM4
CLOSING
TORQUE
Adjusts Closing Torque.
TM5
OPENING
SOFT STOP
Sets the opening slowdown duration
TM6
CLOSING
SOFT STOP
Sets the closing slowdown duration
TM7
AUTO CLOSE
DELAY
Adjusts Auto Close Delay.
Dip switch SW1
1
EMERGENCY
ON
Enables opening with always closed program.
OFF
Disables opening with always closed program.
2
ELECTRO-LOCK
ON
Enables the electric lock when the automation is closed, regardless
of the selected program.
OFF
Enables the electric lock when the automation is closed only with
the “always closed” program.
3
BATTERY MONITORING
ON
If there is no voltage, the automation performs the manoeuvres
normally. If the battery is flat, the board switches off.
OFF
If there is no voltage, the automation performs the manoeuvres
normally. Before the battery is fully discharged, it performs an
opening manoeuvre.
4
OPENING IN BATTERY
ON
In the event of a power failure, the automation opens and remains
open until the mains voltage is restored (DIP3 must be OFF)
OFF
In the event of a power failure, the automation performs the ma
-
neuvers normally.
5
TCA
INCREASE
ON
With a high flow of passages, the automatic closing time is auto
-
matically increased.
OFF
Function disabled, the automatic closing time remains unchanged.
6
ON
OFF
Keep the Dip switch in OFF
DC19 -