4. Structure of Water Leakage Location Detecting System
The water leakage location detecting system consists of:
①
Water leakage location detector
(
AD-AS-1LCM-A
)
②
Water leakage sensor (AD-LS)
③
Break detection terminal (ZT-L2)
For connections on the terminal block, refer to Attached Drawing 2.
Drawing 2 Water Leakage Location Detecting System
5. External Connection
AD-AS-1LCM-A has a terminal block as shown in Drawing 3. (Make connections securely in conformance to Sections 1 to 5.)
Drawing 3 Layout Drawing of Terminal Block
5-1.Power Connection
AC100
~
240V
(
Variation range in power voltage: AC85
~
264V
)
Before connection, check that the power supply voltage is within the range of use, then, connect it securely to the
terminal block.
*Inputting a power voltage outside the range of use may cause malfunctions and failure of the detector, so care should
be taken.
5-2 Ground Connection
Be sure to ground for interference prevention.
-3-
Water leakage location dete
ctor
AD-AS-1LCM-A
*Power source
AC100V
~
Grounding
General instrumentation cables:
Triplex, twisted wiring conductor: 0.5mm
2
min. in area and 100m max. in length
Triplex, single wiring conductor: φ0.8mm min. and 100m max. in length
Joint box
Contact output
Water leakage location
data output
(
4-20mA output
)
・
Central monitoring board
・
Sequencer signal
・
to
Control circuit
Water Leakage
AC240V
AD-LS Sensor
Break Detection
Terminal ZT-L2
Power
Power source
AC85
~
264V
AC85
~
264V
E
E
G
ro
un
din
g
Inductive sensor
AD-LS
B
ra
id
ed
w
ire
In
su
la
te
d
w
ire
R
es
ista
nc
e
w
ire
Inductive sensor
1
2
3
Water leakage
Water leakag
(*
Contact: 1a)
COM
NO
COM
NO
Break
Break contac
(*Contact:1a)
4-20mA output
+
+
-
-
C
O
M
C
O
M
N
O
N
O
Terminal block (M3)
C-LOOP
contact