Operation  setting  switch  instructions 

AD-AS-1LCM-A 

Water  Leakage  Location  Detector 

N

am

 

mm 

Scale 

 

Unit 

Prepared on 

Prepared by 

Checked  by 

Approved  by 

2010.04 

Factory 

setting 

No 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

Buzzer  soundi

ng 

OFF  :  Activated  ON  :  Not  activated 

Alarm  hold  for  water  leakage  location  indication 

Itihyouji   

OFF  :  Not  activated  ON  :  Activated 

Alarm  hold  for  water  leakage  and  break  relays 

Itihyouji   

OFF  :  Not  activated  ON  :  Activated 

Operation  between  Contact  a  and  Conatct  b  for  water  leakage  relay 

Itihyouji   

OFF  :  Contact  a    ON  :  Contact  b 

Operation  between  Contact  a  and  Contact  b  for  break  relay 

Itihyouji   

OFF  :  Contact  a    ON  :  Contact  b 

4-20mA  operation 
OFF   

in  the  case  of  water  leakage  detection:  6+0.03×water  leakage  location  indication  (m)  mA

 

ON 

in  the  case  of  water  leakage  detection:    4+16×water  leakage  location  indication  (m)/250  mA 

Ex:  Water  leakage  is  located  at  100m  :  6+0.03×100  =  9mA 

Ex:  Water  leakage  is  located  at  100m  :  4+16×100/250  =  10.4mA 

Detection  sensitivity  shifting   

  OFF 

    OFF        Standard  sensitivity          Approx.  25kΩ 

ON   

    OFF        Low  sensitivity                  Approx.  10kΩ 

  OFF 

    ON          High  sensitivity                  Approx.  50kΩ 

ON   

    ON          Highest  sensitivity            Approx.  100kΩ 

*Changing  setting  of  switches  corresponidngly  chang  operations  such  as  indication  and  relay. 

If  it  is  changed  to  no  function  status,  no  corresponding  operation  is  activated  ,so  care  should  be  taken. 

(7)              (8) 

Operation

 

O

N

 

 





TTS-KS-W3287-0 

Summary of Contents for AD-AS-1LCM-A

Page 1: ...TTS KS W5010 1 Water Leakage Location Detector AD AS 1LCM A Operation Manual TATSUTA Electric Wire Cable Co Ltd Electronics Division System Department...

Page 2: ...arranty Before the delivery this product is subjected to strict quality control and inspection In the event of spontaneous failure resulting from defective manufacturing we will repair or replace it a...

Page 3: ...r Water Leakage Detection Function 7 Operation Chart 7 8 7 1 Standard Operation Chart 7 2 Operation Chart When Alarm Hold Setting is Activated 8 Indication of Detector Number 9 9 Detection Sensitivity...

Page 4: ...ght up when a break is detected Described on page 6 and 7 Alarm Cancel Switch Used for canceling alarm when the alarm hold setting is activated for indication or the control output contacts Buzzer Sto...

Page 5: ...AD LS Sensor This will cause serious errors in the location detection function So pls make sure not to use or use together with any sensor other than AD LS sensor 2 2 Handling Precautions 1 Use the de...

Page 6: ...power voltage outside the range of use may cause malfunctions and failure of the detector so care should be taken 5 2 Ground Connection Be sure to ground for interference prevention 3 Water leakage l...

Page 7: ...onfiguration Element Configuration Electrode 1 0 33 mm 2 tinned soft copper wire covered with red plastic braided thread Electrode 2 0 5 mm 2 tinned soft copper wire insulated with green plastic Elect...

Page 8: ...age and Break Contact Operation Alarm hold Turning the Operation switch 3 ON activates the alarm hold setting Refer to Drawing 8 1 2 3 4 6 7 8 5 Drawing 8 Alarm Hold Setting for Water Leakage and Brea...

Page 9: ...ibed below Check the facilities Detector Wiring connection among external analog input devices is broken or the input resistance for external analog input devices is more than 500 The internal power i...

Page 10: ...the terminal block again Drawing 13 Indication in the Case of Break Detection 6 3 Check for Water Leakage Detection Function 1 Drop tap water into the water leakage sensor 2 The buzzer sounds the Alar...

Page 11: ...uzzer Stop Switch Buzzer sounding Control output contact water leakage COM NO Control output contact break COM NO Water leakage location indication Sensor length indication Water leakage location data...

Page 12: ...larm indicator LED Buzzer Stop Switch Buzzer sounding Alarm cancel switch Control output contact water leakage COM NO Control output contact break COM NO Water leakage location indication Water leakag...

Page 13: ...ctor Number Setting Switch and select a number that you want to indicate Refer to Attached Drawing 19 The detector number is indicated on the leftmost 7 segment LED 1 9 A B C D E F The factory setting...

Page 14: ...rounding Check Subsection 11 2 control output contact specifications Sensor applied voltage AC5 5V max Working ambient temperature 0 C to 50 C no icing Working ambient humidity 35 RH to 85 RH no conde...

Page 15: ...level etc Buzzer Average sound pressure 90 dB 10 cm sample value by manufacturer Control output contact Contact Configu ration Contacts For specifications refer to Section 3 3 Water leakage 1 for 1a B...

Page 16: ...5 180 RESET BUZZER STOP POWER ALARM 35 Attached Drawing 1 Approved by Prepared by Scale Unit Prepared on Tatsuta Electric Wire Cable Co Ltd Water Leakage Location Detector mm 2010 04 Name Drawing No A...

Page 17: ...h Terminal block M3 Detector number indication Sensor length and water leakage indication Power source indication LED Alarm indication LED Alarm cancel switch Buzzer stop switch Power AC85V AC264V E G...

Page 18: ...Operation between Contact a and Contact b for break relay Itihyouji OFF Contact a ON Contact b 4 20mA operation OFF in the case of water leakage detection 6 0 03 water leakage location indication m mA...

Page 19: ...f Water leakage detection Indicating sensor length Lighting out Lighting out Lighting out Flashing Lighting out Lighting out Alarm LED status Indicating the water leakage location Under normal sensor...

Page 20: ...ber of each detector when multiple detectors are used together Turn the Detector Number Setting Switch to select a number that you want to indicate The detector number is indicated on the leftmost 7 s...

Reviews: