Installation and Handling Precautions
2-1 Installation
The Water Leakage Position Detector (AD-AS-1LCM-A) shall be securely installed in a strong housing, on the wall, etc.
inside a building.
)
Be sure to follow the instructions below when installing this product.
1) Avoid installing the detector in any location subject to high temperature and high humidity, excessively dusty
environments and corrosive gas environments.
2
)
Install the detector in a location that is free from vibration, away from sources of interference such as power switches,
and convenient for quick maintenance and regular inspection.
3
)
Install the inductive sensor using the suitable fixator, according to installation location and environment.
4) Consult with us in case the inductive sensor is used in places easy to be affected by electromagnetic induction.
5) Do not insert foreign matters, including screw-drivers into gaps in the detector.
6) Do not use the sensor as electric wire.
7) Never use inductive sensors other than our product AD-LS Sensor. This will cause serious errors in the location
detection function. So pls make sure not to use or use together with any sensor other than AD-LS sensor.
2-2 Handling Precautions
1
)
Use the detector in an environment with a temperature range between -10˚C and 50˚C and a humidity range between 35%
to 85%.
2
)
Do not use the detector in any location close to sources of vibration and harmful gas, and strong electromagnetic
inductive power sources.
3
)
After installation, be sure to apply the insulating sheet to the terminal block, and cover the surface cover plate,
meanwhile confirm the operation.
3. Maintenance and Periodic Inspection
②
When inspecting the facilities, conduct inspections in conformance with the operation check items described in
Chapter 6.
Note
)
During inspection of the detector, the control output contacts are functioning, so if the control output contacts
are used, disconnect the wiring or connect temporary wiring in order not to affect other devices.
②
If the surface and inside of the sensor is adherent with water repellant substances like oil, normal operation is
possible to be interfered. Please pay attention.
②
If the sensor is tainted with dirty water, please replace it in time.
-2-