Warm Applicable Water accumulator (boiler)
FIRPLACE
Water jacket fireplace
CH
Central heating system
T1
Upper temperature sensor of WAW
T2
Lower temperature sensor of WAW
T3
Temperature sensor of fireplace water jacket
P1
Pump supplying WAW from fireplace
P2
Pump of the primary side of heat exchanger
(it operates if P1 and P3 are activated)
P3
Circulating pump CH
PP
Electronically controlled air throttle of fireplace
2.1
Air throttle operation
2.2 Pump CH operation
2.3 Pump WAW operation
Connection cable of regulator may be replaced only
by producer or his authorized service locations
WARRANTY
WARNING !
ANY MODIFICATION OF THE REGULATOR MADE BY USER CAN BE
THE CAUSE OF SAFETY CONDITIONS DETERIORATION AND CAN
EXPOSE THE USER TO ELECTRIC SHOCK OR DAMAGE DEVICES
SUPPLIED
.
Date of sale
Seller's signature and stamp
Zakład elektroniczny TATAREK Jerzy Tatarek
50-559 Wroclaw, 75 Swieradowska st
ph. (071) 367-21-67, 373-14-88, fax 373-14-58; tax index number 899-020-21-48;
Bank account : BZ WBK S.A. O/WROCŁAW 6910901522-0000-0000-5201-9335
www.tatarek.com.pl.; E-mail: [email protected]
1.Warranty is valid [24] months from the date of sale.
2.Producer does not take responsibility for any mechanical damages made by user.
3.MAKING REPAIRS OR MODYFYING THE DEVICE BY USER IS
FORBIDDEN AND CAUSES WARRANTY CANCELATION
4.Warranty card is valid only with date of sale, seller's signature and stamp
5.Warranty and after-warranty repairs should be done only by producer, damaged
regulators should be sent to producer in order to make all repairs needed.
6.Warranty protection involves the EU
7.Warranty does not exclude, not restrict and not suspend buyer’s rights coming from
the incompatibility of the article with the agreement (Laws Journal No. 141 Pos. 1176)
WARNING!
1. Producer does not take the responsibility for damage
caused by atmospheric discharge
2. and overvoltage in the mains
3. Burnt fuses are not subject to warranty replacement
Register No.. GIOS: E 0002240WZ
Worn out electronic
and electric devices must be transfered to
the utilization collection place, where will
be accepted for free
ARGO-FILM
Recycling Plant No. 6
180 Krakowska st., 52-015 Wroclaw
ph.: 071 794 43 01,
0 515 122 142
The throttle regulates an air supply to the combustion chamber, which allows the temperature of
fireplace water jacket to be kept at set value. The task is realized by comparing temperature (T3) and
set temperature (”
T.Firep
” parameter) and then by gradual opening/shutting the throttle.
The change of a throttle position takes place cyclically every 20 secs (”
Ti.Pause
” parameter). During
the movement the control lamp (9) is lit. The blinking means the drive overload because of met
resistances.
The shutdown of the regulator automatically causes the throttle to be set at rest position defined by
“
ModeOFF
” parameter (Factory setting is 0% - full shut-off).
o
If fireplace temperature exceeds a set value of 45 C (”
T.CH.ON
” parameter) the pump CH turns on.
The switch-off of the pump below the value causes a faster heating of the water jacket above the dew
point and by that a longer life-time of the fireplace.
During supplying the warm applicable water accumulator WAW, the pump can operate cyclically if
the WAW priority is set (Limitation of the heat amount flowing into the system CH).
The cyclical operation is based on turning on the pump for 45 secs and then turning off for 4min
(”
Ti.EndCH
” parameter).
The regulator protects the system from freezing, automatically turning on the circulating pump if the
o
measured temperature is below 4 C.
The regulator realizes the after season rundown of the pump by switching it on for 1 min if it doesn’t
operate for a week.
The regulator controls as well the pump supplying the warm applicable water accumulator WAW.
o
The pump WAW is to turn on if water temperature in fireplace is higher than the threshold of 45 C
o
(”
T.WAW.ON
” parameter) and higher than in the accumulator WAW by 5 C (”
DeltaWAW
”
o
parameter). If WAW temperature exceeds 65 C (”
T.maxWAW
” parameter) the pump WAW turns off.
There are 2 ways of supplying the accumulator WAW: