TATAREK RT-08K User Manual Download Page 6

6

7

CWU

80

o

68

o

Upper temperature sensor T1 (if available)

Lower temperature sensor T2

It

s a stable state that is in order to change it one needs to press the WYBIERZ button

Screen of whole system operation

On the screen are the symbols of devices:
KOM- fireplace
CO - central heating system
CWU - applicable warm water accumulator
$ - if the relay CONTROL is switched on

The symbols (every few seconds or after pressing USTAW button) are replaced with numbers
presenting the temperatures of those devices.
The blinking arrows mean the actual heat flow as an effect of pumps operation:
KOM->CWU the pump P1supplying the CWU accumulator is turned on.
KOM->CO the pump P3 is turned on.

fireplace sensor

80

o

73

o

68

o

If the summer mode is active (only CWU), LATO replaces CO.
It

s a stable screen that is in order to change it one needs to press the WYBIERZ button

CO

$

KOM->CWU

Screen of CWU operation mode

TrybCWU

LATO

In the regulator one can set

TrybCWU

parameter achieving different strategies of operation.

Possible modes are:

The pump CWU turned off

Turning off the heating system in summer time (the pump CO doesn

t operate). Fireplace

only works in the preparation function CWU.

Standard operation (parallel operation of pumps) without favouring the CWU circuit

Faster reaching the readiness of CWU accumulator by limiting heat obtain by heating

system. The pump CO works cyclically. Turning off the pump CWU after supplying the accumulator
causes the comeback of normal operation of the pump CO

beyond time zones the pump operates like in the ZA

Ł

mode and in the time zone like PRIO

WY

Ł

-

LATO-

ZA

Ł

-

PRIO-

ZEGAR-

Screen of clock

The screen shows the actual time and the number of active time zone.

Time correction is possible after pressing the USTAW button (5) and the minutes field begins
blinking. The blinking value can be altered with the buttons

+

or

-

. Pressing the WYBIERZ

button (3) one comes to the hours field that can be set with the buttons

+

or

-

.

Pressing the USTAW button confirms the changes (the clock field will stop blinking).

ZEGAR $1

17:15

PoziomUS

0

Screen of setting the parameters

Normally the parameters setting level equals to

0

namely the parameters aren

t available.

After changing the level to

1

,

2

or

3

successive screens show the values of parameters.

The last screen contains

****

after which it comes back to the above mentioned screens.

30...60

o

C

50

o

C

20...85

o

C

50

o

C

30...100

o

C

65

o

C

30...100

o

C

50

o

C

1...10

o

C

2

o

C

T za

Ł

CO

Tza

Ł

CWU

Tmax CWU

Tmin CWU

DeltaCWU

0:00...23:45

6:00

0:00...23:45

8:00

:00...23:45

14:00

0:00...23:45

17:30

0:00...23:45

20:00

0:00...23:45

22:30

0

CONTROL relay is turned on.

upper sensor of CWU

lower sensor of CWU

PARAMETERS OF LEVEL 1

FUNCTION

NAME

RANGE

FACTORY
SETTING

Minimal temperature of fireplace at which the pump P3(CO)
is activated.
Minimal temperature of fireplace at which the pump P1(CWU)
turns on.
Maximal temperature of CWU accumulator. The exceeding

turns off the supply pump

Minimal temperature of CWU accumulator. The exceeding
turns on the supply pump
Minimal difference between fireplace and CWU accumulator
temperature needed for the pump operation P1 (CWU)

PARAMETERS OF LEVEL 2

FUNCTION

NAME

RANGE

FACTORY
SETTING

STRF1 from
STRF1 till
STRF2 from
STRF2 till
STRF3 from
STRF3 till

Start of 1st time zone

End of 1st time zone

Start of 2nd time zone
End of 2nd time zone
Start of 3rd time zone
End of 3rd time zone