10
3
CWU
Applicable Warm Water Accumulator (boiler)
KOM
Water jacket fireplace
CO
Central heating system
T1
Upper temperature sensor of solar collector
T2
Lower temperature sensor of CWU
T3
Temperature sensor of fireplace water jacket
P1
Pump supplying CWU from fireplace
P2
Pump of the primary side of heat exchanger (it operates if P1 and P3 are activated)
P3
Circulating pump CO
2.1 Pump CO operation
2.2 Pump CWU operation
2.3 CWU priority and summer mode
In the regulator one can set
“
TrybCWU
”
parameter achieving different strategies of operation.
Possible modes are:
The pump CWU turned off
Turning off the heating system in summer time (the pump CO doesn
’
t operate). Fireplace
only works in the preparation function CWU.
Standard operation (parallel operation of pumps) without favouring the CWU circuit
WYŁ -
LATO-
ZAŁ -
If fireplace temperature exceeds a set value of 45 C (
”
T.za
ł
CO
”
parameter) the pump CO turns on.
The switch-off of the pump below the value causes a faster heating of the water jacket above the dew
point and by that a longer life-time of the fireplace.
During supplying the applicable warm water accumulator CWU, the pump can operate cyclically if
the CWU priority is set (Limitation of the heat amount flowing into the system CO).
The cyclical operation is based on turning on the pump for 45 secs and then turning off for 4min
(
”
t.stopCO
”
parameter).
The regulator realizes the after season rundown of the pump by switching it on for 1 min if it doesn
’
t
operate for a week.
o
The regulator protects the system from freezing, automatically turning on the circulating pump if the
measured temperature is below 4 C.
o
The regulator controls as well the pump supplying the applicable warm water accumulator CWU.
The pump CWU is to turn on if water temperature in fireplace is higher than the threshold of 45 C
(
”
T.za
ł
CWU
”
parameter) and higher than in the accumulator CWU by 5 C (
”
DeltaCWU
”
parameter). If CWU temperature exceeds 65 C (
”
T.maxCWU
”
parameter) the pump CWU turns off.
There are 2 ways of supplying the accumulator CWU:
65 C
(
„
TmaxCWU
”
parameter )
Optimal supply (Parameter
”
SterCWU
”
=2) - from partial discharge to max supply. The
supply turns on if the upper temperature sensor of CWU (T1) shows temperature lower than 50 C
(
”
TminCWU
”
parameter) and turns off if the lower temperature sensor of CWU (T2) shows
temperature higher than 65 C (
”
TmaxCWU
”
parameter)
The regulator realizes the after season rundown of the pump by switching it on for 1 min if it doesn
’
t
operate for a week.
o
o
o
o
o
o
?
?
Keeping the accumulator CWU at maximal readiness (Parameter ”SterCWU”=1).
The supply starts if the lower temperature sensor of CWU (T2) shows temperature below
Connection cable of regulator may be replaced only
by producer or his authorized service locations
WARRANTY
W
ARNING !
ANY MODIFICATION OF THE REGULATOR MADE BY USER CAN BE
THE CAUSE OF SAFETY CONDITIONS DETERIORATION AND CAN
EXPOSE THE USER TO ELECTRIC SHOCK OR DAMAGE DEVICES
SUPPLIED
.
Date of sale
Seller's signature and stamp
Zak
ł
ad elektroniczny TATAREK Jerzy Tatarek
50-559 Wroclaw, 75 Swieradowska st
ph. (071) 367-21-67, 373-14-88, fax 373-14-58; tax index number 899-020-21-48;
Bank account : BZ WBK S.A. O/WROC
Ł
AW 6910901522-0000-0000-5201-9335
www.tatarek.com.pl.; E-mail: [email protected]
1.Warranty is valid [24] months from the date of sale.
2.Producer does not take responsibility for any mechanical damages made by user.
3.MAKING REPAIRS OR MODYFYING THE DEVICE BY USER IS
FORBIDDEN AND CAUSES WARRANTY CANCELATION
4.Warranty card is valid only with date of sale, seller's signature and stamp
5.Warranty and after-warranty repairs should be done only by producer, damaged
regulators should be sent to producer in order to make all repairs needed.
6.Warranty protection involves the EU
7.Warranty does not exclude, not restrict and not suspend buyer
’
s rights coming from
the incompatibility of the article with the agreement (Laws Journal No. 141 Pos. 1176)
WARNING!
1. Producer does not take the responsibility for damage
caused by atmospheric discharge
2. and overvoltage in the mains
3. Burnt fuses are not subject to warranty replacement
Register No.. GIOS: E 0002240WZ
Worn out electronic
and electric devices must be transfered to
the utilization collection place, where will
be accepted for free
ARGO-FILM
Recycling Plant No. 6
180 Krakowska st., 52-015 Wroclaw
ph.: 071 794 43 01,
0 515 122 142