TATAREK RT-08K User Manual Download Page 3

10

3

CWU

Applicable Warm Water Accumulator (boiler)

KOM

Water jacket fireplace

CO

Central heating system

T1

Upper temperature sensor of solar collector

T2

Lower temperature sensor of CWU

T3

Temperature sensor of fireplace water jacket

P1

Pump supplying CWU from fireplace

P2

Pump of the primary side of heat exchanger (it operates if P1 and P3 are activated)

P3

Circulating pump CO

2.1 Pump CO operation

2.2 Pump CWU operation

2.3 CWU priority and summer mode

In the regulator one can set

TrybCWU

parameter achieving different strategies of operation.

Possible modes are:

The pump CWU turned off

Turning off the heating system in summer time (the pump CO doesn

t operate). Fireplace

only works in the preparation function CWU.

Standard operation (parallel operation of pumps) without favouring the CWU circuit

WYŁ -
LATO-

ZAŁ -

If fireplace temperature exceeds a set value of 45 C (

T.za

ł

CO

parameter) the pump CO turns on.

The switch-off of the pump below the value causes a faster heating of the water jacket above the dew
point and by that a longer life-time of the fireplace.
During supplying the applicable warm water accumulator CWU, the pump can operate cyclically if
the CWU priority is set (Limitation of the heat amount flowing into the system CO).
The cyclical operation is based on turning on the pump for 45 secs and then turning off for 4min
(

t.stopCO

parameter).

The regulator realizes the after season rundown of the pump by switching it on for 1 min if it doesn

t

operate for a week.

o

The regulator protects the system from freezing, automatically turning on the circulating pump if the
measured temperature is below 4 C.

o

The regulator controls as well the pump supplying the applicable warm water accumulator CWU.
The pump CWU is to turn on if water temperature in fireplace is higher than the threshold of 45 C
(

T.za

ł

CWU

parameter) and higher than in the accumulator CWU by 5 C (

DeltaCWU

parameter). If CWU temperature exceeds 65 C (

T.maxCWU

parameter) the pump CWU turns off.

There are 2 ways of supplying the accumulator CWU:

65 C

(

TmaxCWU

parameter )

Optimal supply (Parameter

SterCWU

=2) - from partial discharge to max supply. The

supply turns on if the upper temperature sensor of CWU (T1) shows temperature lower than 50 C
(

TminCWU

parameter) and turns off if the lower temperature sensor of CWU (T2) shows

temperature higher than 65 C (

TmaxCWU

parameter)

The regulator realizes the after season rundown of the pump by switching it on for 1 min if it doesn

t

operate for a week.

o

o

o

o

o

o

?

?

Keeping the accumulator CWU at maximal readiness (Parameter ”SterCWU”=1).

The supply starts if the lower temperature sensor of CWU (T2) shows temperature below

Connection cable of regulator may be replaced only

by producer or his authorized service locations

WARRANTY

W

ARNING !

ANY MODIFICATION OF THE REGULATOR MADE BY USER CAN BE
THE CAUSE OF SAFETY CONDITIONS DETERIORATION AND CAN

EXPOSE THE USER TO ELECTRIC SHOCK OR DAMAGE DEVICES
SUPPLIED

.

Date of sale

Seller's signature and stamp

Zak

ł

ad elektroniczny TATAREK Jerzy Tatarek

50-559 Wroclaw, 75 Swieradowska st

ph. (071) 367-21-67, 373-14-88, fax 373-14-58; tax index number 899-020-21-48;

Bank account : BZ WBK S.A. O/WROC

Ł

AW 6910901522-0000-0000-5201-9335

www.tatarek.com.pl.; E-mail: [email protected]

1.Warranty is valid [24] months from the date of sale.
2.Producer does not take responsibility for any mechanical damages made by user.
3.MAKING REPAIRS OR MODYFYING THE DEVICE BY USER IS
FORBIDDEN AND CAUSES WARRANTY CANCELATION
4.Warranty card is valid only with date of sale, seller's signature and stamp
5.Warranty and after-warranty repairs should be done only by producer, damaged
regulators should be sent to producer in order to make all repairs needed.
6.Warranty protection involves the EU
7.Warranty does not exclude, not restrict and not suspend buyer

s rights coming from

the incompatibility of the article with the agreement (Laws Journal No. 141 Pos. 1176)

WARNING!

1. Producer does not take the responsibility for damage
caused by atmospheric discharge
2. and overvoltage in the mains
3. Burnt fuses are not subject to warranty replacement

Register No.. GIOS: E 0002240WZ

Worn out electronic

and electric devices must be transfered to

the utilization collection place, where will

be accepted for free

ARGO-FILM
Recycling Plant No. 6
180 Krakowska st., 52-015 Wroclaw
ph.: 071 794 43 01,

0 515 122 142

Reviews: