7
2.6.1 FOAMJET LX WITH MASTERSTREAM 1000 & 1250s NOZZLE
To increase the expansion ratio, Task Force Tips “Foamjet LX” (model FJ-LX-M) may be used with the Masterstream 1000 and 1250s
nozzles. This low expansion foam tube attaches and detaches quickly from the nozzle. Adjust nozzle spray pattern to give best foam
quality. Note: As expansion ratio is increased, the reach of the nozzle will be decreased due to the greater amount of bubbles in the
stream and their inability to penetrate the air. Generally the reach with foam is approximately 10% less than with water only. Actual
results will vary based on brand of foam, hardness of water, temperature, etc.
Fig 2.6.1 FJ-LX-M Shown on Mastersteam Nozzle
3.0 NOZZLE OPERATION
3.1 AUTOMATIC NOZZLE OPERATION
Automatic nozzles operate by sensing the pressure at the nozzle’s inlet and adjusting the discharge opening to maintain a constant
pressure throughout the fl ow range of the nozzle. For example, when the pressure at the inlet increases, the exit area is automatically
increased until the inlet pressure returns to the nominal pressure of the nozzle.
Note: Inlet pressure of a Masterstream Series automatic nozzle will stabilize at the nominal pressure within 5%. This stabilization may
take as long as half a minute after a change in inlet pressure.
3.1.1 FLOW CHARACTERISTICS OF MASTERSTREAM 1000 & 1250s
Within its fl ow range, the Masterstream 1000 and 1250s automatic nozzles operate at the nominal pressure of 100 PSI (7 BAR, 700
KPA). Figures 2 shows typical performance of this nozzle.
WARNING
Large amounts of debris can reduce the fl ow of the nozzle resulting in an ineffective fl ow. In the
event of a blockage it may be necessary to retreat to a safe area, uncouple nozzle and remove
debris.