background image

©Copyright Task Force Tips LLC   2002 - 2019 

LKB-200 July 29, 2018 Rev01

11

9.2.2  FLOW TESTING

Flow testing must be conducted in the following manner.

1. The nozzle shall be mounted so that the fl ow rate and pressure through the nozzle and the pressure at the inlet can be 
accurately measured.
2. With the shut off  fully open, the inlet pressure shall be adjusted to the rated pressure ±2 percent.
3. Evaluate the fl ow of nozzles as defi ned by NFPA 1964 in the following manner: 

Basic Spray Nozzles shall fl ow no less than and no more than 10 percent over the rated fl ow at the rated pressure in the straight 
stream and wide-angle fog settings.
Constant and Selectable Gallonage Nozzles shall fl ow no less than and no more than 10 percent over the rated fl ow at the rated 
pressure at each predetermined fl ow selection.

1. The valve or shut off  and pattern controls shall be operated through their full range of motion at 100 psi (6.9 bar or 690 kPa) 
with no signs of leaking, binding or other problems.

9.2.3   RECORDS

A record of testing and repairs must be maintained from the time the nozzle is purchased until it is discarded. Each TFT nozzle is 
engraved with a unique serial number which, if so desired, can be used to identify nozzle for documentation purposes.

The following information, if applicable, must be included on the test record for each nozzle:

1. Assigned identifi cation number
2. Manufacturer
3. Product or model designation
4. Vendor
5. Warranty
6. Hose connection size
7. Maximum operating pressure
8. Flow rate or range
9. Date received and date put in service
10. Date of each service test and service test results
11. Damage and repairs, including who made the repairs and the cost of repair parts
12. Reason removed from service

NFPA 1962: Standard for the care, use, inspection, service testing, and replacement of 

fi

 re hose, couplings, nozzles and 

fi

 re hose appliances. 

(2013 ed., Section 5.5.4). Quincy, MA: National Fire Protection Agency.

9.3 REPAIR

Factory  service  is  available  with  repair  time  seldom  exceeding  one  day  in  our  facility.  Factory-serviced  nozzles  are  repaired  by 
experienced technicians to original specifi cations, fully wet tested, and promptly returned. Repair charges for non-warranty items are 
minimal. Any returns should include a note as to the nature of the problem and whom to reach in case of questions.
Repair parts and service procedures are available for those wishing to perform their own repairs. Task Force Tips assumes no liability 
for damage to equipment or injury to personnel that is a result of user service. Contact the factory or visit the web site at www.tft.com 
for parts lists, exploded views, test procedures and troubleshooting guides.
Performance tests shall be conducted on each nozzle after a repair, or anytime a problem is reported to verify operation in accordance 
with TFT test procedures. Consult factory for the procedure that corresponds to the model and serial number of the nozzle. Any 
equipment which fails the related test criteria should be removed from service immediately. Troubleshooting guides are available with 
each test procedure or, equipment can be returned to the factory for service and testing.
All replacement parts must be obtained from the manufacturer to assure proper operation of the product, and to maintain approval 
of the device.

CAUTION

Any alterations to the nozzle and its markings could diminish safety and constitutes a misuse of 
this product.

Summary of Contents for ER Bubble Cup

Page 1: ...s want responders to know and understand the following 1 Firefighting and Emergency Response are inherently dangerous activities requiring proper training in their hazards and the use of extreme caution at all times 2 It is your responsibility to read and understand any user s instructions including purpose and limitations provided with any piece of equipment you may be called upon to use 3 It is y...

Page 2: ...proper training is a misuse of this equipment TASK FORCE TIPS LLC MADE IN USA tft com 3701 Innovation Way Valparaiso IN 46383 9327 USA 800 348 2686 219 462 6161 Fax 219 464 7155 Copyright Task Force Tips LLC 2008 2019 LIY 500 April 8 2019 Rev14 MANUAL Remote Control RC Monitor Electrical Controls Supplemental Instructions for use with RC Monitor Manual INSTRUCTIONS FOR INSTALLATION SAFE OPERATION ...

Page 3: ...ning water Always drain after use to avoid damage and possible loss of use NOTICE To prevent mechanical damage do not drop or throw equipment 1 Electrostatic Hazards of Foam Blanketing Operations by Peter Howels Industrial Fire Safety July August 1993 2 The Fire Fighter and Electrical Equipment The University of Michigan Extension Service Fourth Printing 1983 Page 47 3 1 COMMON MODEL AND TERMS MOT...

Page 4: ...IFICATIONS 3 2 1 MECHANICAL Maximum nozzle operating pressure 100 psi 7 bar Operating temperature range of fluid 33 to 120º F 1 to 50º C Storage temperature range 40 to 150º F 40 to 65º C Materials used Aluminum 6000 series hard anodized MIL8625 class 3 type 2 stainless steel 300 series nylon 6 6 nitrile rubber acrylonitrile styrene acrylate Consult Factory for higher pressure applications 3 3 NOZZ...

Page 5: ...UBBLE CUP Figure 4A 20 95 GPM BUBBLE CUP Figure 4B 4 1 TRAJECTORY CHART 100 PSI RC BUBBLE CUP NOZZLE CURVE GPM FLOW PRESSURE PSI LBS REACTION A 20 100 10 B 60 100 30 C 95 100 48 CURVE LPM FLOW PRESSURE BAR KGf REACTION A 75 6 9 4 5 B 227 6 9 13 6 C 360 6 9 21 7 These trajectories reach and reaction numbers are provided for reference All data based on 30 degree nozzle discharge angle in straight st...

Page 6: ...s and high flow patterns The nozzle can be operated manually by turning the SHAPER clockwise as seen from the operating position behind the nozzle to move to the straight stream position The pattern can be adjusted either by operating the electric actuator or by manually rotating the shaper When operating electrically the shaper will move in slow mode from shutoff to low flow straight stream and stop...

Page 7: ...Flow water to flush if necessary 6 Apply blue loctite to screw threads Reinstall seat baffle spring washer and baffle retaining screw make sure seat is centered on baffle and orient spring washer as shown below 7 Torque baffle retaining screw to 180 in lb 20 N m 5 2 ASPIRATING SLEEVE The Bubble Cup nozzle is capable of producing aspirated foam as well as a conventional straight stream and wide protective f...

Page 8: ...ght Task Force Tips LLC 2002 2019 LKB 200 July 29 2018 Rev01 8 6 0 DRAWINGS AND PART LISTS 14 13 12 11 10 9 8 7 5 6 4 3 2 1 22 20 21 19 17 23 18 5 15 39 16 38 37 36 31 30 29 27 28 16 25 26 40 41 32 24 34 33 35 ...

Page 9: ...72 15 COUPLING 1 5 NH ROCKERLUG 1 F10097N 16 GASKET 2 V3130 17 PORT PLUG 1 B770 18 TIMING BELT 1 F771 19 DOWEL PIN 2 VP250X1 50 20 ROLLER 2 F769 21 ACTUATOR UPPER HOUSING 1 F767 22 TASK FORCE TIPS LOGO LABEL 1 HE195 23 DUST COVER 1 F774 24 3 16 BALL STAINLESS STEEL 34 V2120 25 BASE 1 F760 27 O RING 125 1 VO 125 28 HEAD 20 60 GPM 1 F761 HEAD 20 95 GPM 1 F762 29 QUAD RING 225 1 VOQ 4225 30 SEAT 1 F6...

Page 10: ...n repaired or altered by someone else THIS IS A LIMITED EXPRESS WARRANTY ONLY TFT EXPRESSLY DISCLAIMS WITH RESPECT TO THE EQUIPMENT ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND ALL IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE THERE IS NO WARRANTY OF ANY NATURE MADE BY TFT BEYOND THAT STATED IN THIS DOCUMENT This limited warranty gives you specific legal rights and you may also have other...

Page 11: ...ults 11 Damage and repairs including who made the repairs and the cost of repair parts 12 Reason removed from service NFPA 1962 Standard for the care use inspection service testing and replacement of fire hose couplings nozzles and fire hose appliances 2013 ed Section 5 5 4 Quincy MA National Fire Protection Agency 9 3 REPAIR Factory service is available with repair time seldom exceeding one day i...

Page 12: ...on if applicable 9 There is no damage to the nozzle tip 10 The shut off valve if so equipped operates as designed and shuts the flow off completely BEFORE BEING PLACED BACK IN SERVICE nozzles must be inspected to this checklist 1 All controls and adjustments are operational 2 Shut off valve if so equipped closes off the flow completely 3 There are no broken or missing parts 4 There is no damage to the n...