Specifications:
• Feed-back Voltage: 1-Ph, 2-wire (Phase-to-Phase), Nom. 415 Volts.
(User Settable Range: 110 to 480 Vac, in step of 1 Volt).
• Supply Current Feedback (CT) I/P: Selectable Nom. 1 Amp or 5 Amp.
• Measurement Accuracy: Class 2.
• Auxiliary Operating Supply: 1-Ph, 2-wire (Phase-to- Neutral),
Nominal 240 Volts, 50 Hz, or Nominal 120 Volts, 60 Hz.
• Feed-back Voltage and Mains AC Supply Frequency Range:
47 Hz to 53 Hz. (Nom. 50 Hz) or 57 Hz to 63 Hz (Nom. 60 Hz).
• P. F. Correction Cycle Time Range:
User Selectable:1 Second to 600 Seconds, in step of 1 Second.
• Capacitor Bank Discharge Time Range:
Power Factor Controller APFC 06
• Capacitor Bank Discharge Time Range:
User Selectable:1 Second to 600 Seconds, in step of 1 Second.
• Output commands: 4 or 6 or 8 or 12 Relay N.O. Contacts Outputs.
(Isolated ‘N.O.’ Relay Contacts of rating 5 Amp (Resistive Load) /
0.5Amp (Inductive Load)/ 230Vac, suitable for Three-Phase
Capacitor-Duty Contactor Coils of nominal 230 Vac, 50 Hz).
• Operating Temperature Range: +5
o
C. to +60
o
C.
• Class-2 power measurement accuracy operating temp.
+5
o
C to +50
o
C
• Storage Temperature Range: -5
o
C to +65
o
C.
• Relative Humidity Range: 10% to 90% RH Non-Condensing.