Control wiring diagram :
Power Factor Controller APFC 06
Quadrature Mode Connection : Use any two phases for voltage monitoring and use the third phase
for the current monitoring.
Fuse 3.0 A,
Fast Blow
Fuse 0.5 A,
Slow Blow
Fuse 5.0 A,
Fast Blow
Aux.
Input
supply
- 10 -
Either of the above specified schemes, Scheme-1 or
Scheme-2 can be selected by the user, based on the
system requirement.
APFC - 06
C1 C2 C3 C4 --------- -C12
SUPPLY
2A
R-C Snubber across contactor coil:
It is
recommended
to install R-C Snubber across the 110-240 V AC Rated Contactor Coil, for
APFC-06 relay contacts reliability and operational reliability.
The recommended values for the Series Connected Resistor & Capacitor ( R & C) Components
are: R =330 Ohm, +/- 5%, 1 Watt, CFR Type. C = 0.1 micro-farad / 1000 V DC.