Power Factor Controller APFC 06
EDIT PARAMETERS : MINIMUM , MAXIMUM AND DEFAULT VALUES
PARAMETER
MIN
MAX
INCREMENT /
DECREMENT
STEP SIZE
FACTORY
DEFAULT
FAULTS
13] Temperature Fault (Internal to APFC Unit)
Disable: 0
Indicate: 1
Off Step: 2
Off Fixed : 3
Fast Off : 4
0
4
1
0
14] Temperature Resume (Deg. C)
0
Set Upper
Limit
1
55
15] Temperature Limit (Trip) (Deg. C.)
Set Lower
Limit
99
1
65
16] Step Health Check
(Enable: 1/ Disable: 0)
0
1
1
0
17] Bank kVAr Fault Tolerance
0
60
1
10
18] Bank kW Fault Tolerance
0
60
1
10
- 33 -
18] Bank kW Fault Tolerance
0
60
1
10
19] FAN O/P ACTION
(Enable: 1/ Disable: 0)
0
1
1
0
20] FAN ON TEMPER. Action, Degree C.
0
100
1
> = +40
21] FAN OFF TEMPER. Action, Degree C.
0
100
1
= < +30
22] PF Aux. O/P ACT.
0
1
1
0
23] PF Alarm Set
0.85
0.97
0.01
0.90
24] PF Alarm Resume
0.90
0.99
0.01
0.95