Power Factor Controller APFC 06
EDIT PARAMETERS : MINIMUM , MAXIMUM AND DEFAULT VALUES
PARAMETER
MIN
MAX
STEP
SIZE
FACTORY
DEFAULT
STEPS
1] Steps Connected, as per ordered Model
01
04 / 06 / 08 / 12
1
As per Ordered.
2] Default Mode
(Auto: 0/ Manual:1)
0
1
1
0
3] Compensation kVAr
(Instant: 0/ Mean: 1)
0
1
1
1
4] Cap Bank Voltage (L-L)
100
65530
1
415 V
5] Correction Time (Seconds)
1
600
1
120
6] Discharge Time (Seconds)
1
600
1
60
7] Step Response Cycles
45
45
8] Interleaving Delay (Seconds)
1
9
1
1
9] Fix-bank Setting
10] Bin/C/E Series Bank kVAr
1
250
1
020
11] Ext Fix Bank kVAr
000
999
1
000
- 34 -
11] Ext Fix Bank kVAr
000
999
1
000
12] Correction Type
Binary: 0
Un-Equal: 1
C-series: 2
E-Series: 3
0
3
1
2
13] C-Series (Selectable from 0 to 9)
0
9
1
00
14] E-Series
11111222
15] Unequal Bank [1] kVAr
0001
250
1
001
16] Unequal Bank [2] kVAr
0001
250
1
002
17] Unequal Bank [3] kVAr
0001
250
1
004
18] Unequal Bank [4] kVAr
0001
250
1
005
19] Unequal Bank [5] kVAr
0001
250
1
010
‘ ---------
‘ ---------
26] Unequal Bank [12] kVAr
0001
250
1
050