background image

Release 08/2007 Ver. 2.0 

 

Technical Manual: C6 Multifunction Interface Controller

  

TAPESWITCH CORPORATION

 

 

Phone: 631-630-0442 

100 Schmitt Boulevard 

12

 

Fax: 631-630-0454 

Farmingdale, New York 1735 

 

www.tapeswitch.com 

4.3 Monitor Output 
 

Non-safety  monitor  outputs  are  also  provided  for  all 
six  zones.  These  outputs  can  be  configured  either 
normally  open  or  normally  closed.  The  monitor 
outputs should be wired in such a way to indicate the 
status of both safety output relays.  As an example, if 
both  safety  outputs  are  connected  as  normally  open 
(contacts  closed  when  the  mat  and  or  light  curtain  is 
clear)  the  monitor  relay  output  should  be  wired  as 
normally  closed.  Therefore,  when  the  safety  outputs 
are  open  (contacts  open  when  the  mat  and  or  light 
curtain  are  activated),  the  monitor  outputs  will  be 
closed.  These  outputs  can  be  used  for  non-safety 
related  functions  such  as  displays  and  status 
indications.  It  must  not  be  used  for  safety  related 
machine control and switching functions. 
 
 

C6 - TECHNICAL SPECIFICATIONS

 

 

MODEL STYLE

C6 Multifunction Controller

Part Number

0480

Supply Voltage

110-240 VAC 50/60 Hz or 24 VDC

Power

Consumption

30VA TYPICAL

Enclosure Type

Metal Wall Mount

Protection Rating

NEMA 1 Standard / IP10, NEMA
12 Optional  / IP52

Weight

9.5 lbs. 

(4.3 kg)

Sensor Wiring

Fail-Safe

Reset Mode

Automatic (supplied) or

Manual Reset or Combination

Outputs Relays

Forced Guided Safety Relays

Output Contacts

6.0A @ 240 VAC Resistive Load

Monitor Output

Non-Safety 6 X (N/O or N/C)

Selectable, 10A @ 250 VAC

Resistive

Applications

Light curtains, ribbon switches,

sensing edges/bumpers, switching

mats

Operating

Temperature

o

C to 50 

o

C

Response Time

10ms

 

 
 

4.4 Printed Circuit Board LEDS 
 

On  the  main  printed  circuit  board,  adjacent  to  the 
sensor/ light curtain terminal blocks are a series of red 
LEDS. The LEDS are placed in pairs to coincide with 
the  location  of  the  inputs  of  the  sensors  and  light 
curtains. The purpose of these LEDS is to indicate the 
status of the sensing device that is being used. If both 
LEDS  are  illuminated,  this  indicates  that  the  sensing 
device  is  open  or  clear.  If  both  LEDS  are  off,  this 
indicated that the sensing device is closed or blocked. 
If  only  one  of  the  LEDS  is  illuminated,  this  indicates 
that  there  is  a  problem  with  the  sensor  wiring  or 
sensor (mat, edge, and bumper, etc.). In a light curtain 
application  a  single  LED  will  indicate  that  one  of  the 
receiver outputs is inoperative or not connected. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for C6

Page 1: ...they are correctly fitted to a suitable machine It is essential that the full contents of this manual and all the international documents referred to herein are fully understood before any attempt at...

Page 2: ...ork 1735 www tapeswitch com CONTENTS Page 1 INTRODUCTION 3 2 METHODS OF INTERFACING 3 3 ELECTRICAL CONNECTIONS 4 3 1 Reset Manual Automatic 3 2 Pressure Sensitive Sensor s Connections 3 3 Mechanical 3...

Page 3: ...two closed contacts will open when the sensing device is actuated i e safety mat is stepped on or should a fault occur within the safety device or in the event that the power is removed The outputs wi...

Page 4: ...e g as an input to a PLC To protect the contacts of the safety output relays from the effects of switching inductive loads an appropriately rated power factor correction device must be installed for t...

Page 5: ...on Wiring Diagram taking particular care that there are no stray strands which could cause a short between the adjacent terminals A number of sensors can be connected in series See Figure 6 for detail...

Page 6: ...O N C N O CTR N C N O CTR N C CTR N O N C N O CTR N C N O Safety O P 1 Safety O P 2 Monitor O P 1 Monitor O P 2 Monitor O P 3 Monitor O P 4 Monitor O P 5 Monitor O P 6 M AT 1 GUARD 1 MAT 2 M AT 3 MAT...

Page 7: ...ensor 2 Edge sensor N SMOOTH 1 RIBBED 1 SMO RIB C D B A SMOOTH SMOOTH 2 RIBBED RIBBED 2 SMO SMO SMO RIB RIB RIB Edge sensor 1 Edge sensor N Edge sensor 2 INTERCONNECT DIAGRAMS DAISY CHAINED SERIES CON...

Page 8: ...Controller Safety Outputs to Machine Controls Power Input Zone 6 Zone 5 Zone 4 Zone 2 or Sensor 1 Emitter 1 Receiver 1 W1 W2 Zone 1 Sensor 2 or Receiver 2 Emitter 2 W2A W1A Zone 3 Sensor 3 or Emitter...

Page 9: ...W 2 Gray Output 2 5 G1B W 2 Pink Data 6 Isolate 6 7 No Connection W 2 Blue Data 7 Isolate 6 7 No Connection W 2 Shield Ground 8 COM Cable Cable Type Color Code Function From Light Curtain 2 C6 to Guar...

Page 10: ...V DC 2 COM W 1 B Blue Test Out TWIST PAIR TOGETHER Black Blue Wire No Connection W 1 B Black Test In No Connection W 1 B Gray Ground 5 COM RKT8 09 XX Receiver 8 Pin Quick Disconnect W 2 B White OV DC...

Page 11: ...even if the sensors and or light curtain is cleared until the key switch reset is applied 4 Once the reset is applied the flashing red light s for the activated zone s will turn off and the six green...

Page 12: ...C Power Consumption 30VA TYPICAL Enclosure Type Metal Wall Mount Protection Rating NEMA 1 Standard IP10 NEMA 12 Optional IP52 Weight 9 5 lbs 4 3 kg Sensor Wiring Fail Safe Reset Mode Automatic supplie...

Page 13: ...100 Schmitt Blvd Farmingdale NY 11735 Toll Free 1 800 234 8273 Tapeswitch CORPORATION MANUAL MODE OUTPUT OFF OUTPUT ON C 6 M U L T IF U N C T IO N C O N T R O L E R C6 Multifunction Controller C6 10M...

Reviews: