Hardware Set up

The following describes the hardware configuration required 

for proper 2-stage thermostat operation. For complete 
controller installation details, please see TC-1 Installation 

Guide and related advisories. 

Power the TC-1 via appropriate mains voltage and 
wire per TC-1 Installation Instructions. 

Attached a TP-1 temperature probe to the controller's 

probe bus. Install a TP-1 temperature probe in an 
appropriate location for sensing glycol temperature. 

Use shielded CAT-5 cable to extended the probe 
cables as needed being sure to ground the shield only 

inside controller. Do not exceed 50' of  total probe 
cable length. If using two probes, be sure to attach 

the probes in a bus topology (e.g., from  controller to 
TP-1 and then from TP-1 to TP-2). Make all cable 

splices as close to the probes as possible and use only 
moisture-proof, gel-filled IDC connectors for splices. 

Ensure that shield is contiguous from controller 
through to TP-2. 

Wire RELAY 1 to the solenoid or valve that controls 

STAGE 1 of the chiller

Wire RELAY 2 to the solenoid or valve that controls 
STAGE 2 of the chiller

Attach network cable to the controller per Echelon FT 

wiring guide. Networking is optional.

 

Software Set up

Enter program mode by pressing and releasing the 
PGM button

Press the PGM button to advance to the 'CC' and turn 

this menu item 'On' via the UP or DOWN button

Press the PGM button to advance to 'diF' (thermostat 
differential) and adjust as desired via UP/DOWN 
buttons

Summary of Contents for TC-1

Page 1: ...TC 1 Controller USER S GUIDE ADDENDUM 2 Stage Cool Mode Firmware Version 3 93 ...

Page 2: ...r EF accessible under the CC menu is enabled During programming C2 mode is indicated by the illumination of both the COOL and AUTO front panel LEDs and by the characters C2 displayed in the temperature window During operating mode the COOL and AUTO LEDs illuminate while glycol temperature is displayed in the Temperature window In multiple temperature probe applications the controlling temperature ...

Page 3: ... If using two probes be sure to attach the probes in a bus topology e g from controller to TP 1 and then from TP 1 to TP 2 Make all cable splices as close to the probes as possible and use only moisture proof gel filled IDC connectors for splices Ensure that shield is contiguous from controller through to TP 2 Wire RELAY 1 to the solenoid or valve that controls STAGE 1 of the chiller Wire RELAY 2 ...

Page 4: ... Press the PGM button to advance to dCH dual zone cool heat and turn this setting On via the UP or DOWN button ...

Page 5: ...dvance to MODE selection as indicated by a blinking MODE light or the word OFF blinking in the SETPOINT window Prese the UP or DOWN button to select the desired thermostat MODE either COOL or HEAT Notes Only COOL and HEAT modes are affected when dCH is set to On Also the following parameters are ignored by the thermostat when dCH is set to On CP HP and Hr Please see TC 1 User s Guide for more info...

Page 6: ...ed in the TEMPERATURE display window Press the UP DOWN buttons to adjust SP2 to the desired value as shown in the SETPOINT display window Adjusting SP1 and SP2 Simultaneously Press and hold the PGM button While holding the PGM button depressed use the UP and DOWN buttons to adjust SP1 to the desired value as indicated in the SETPOINT window The value of SP2 also changes by this same amount despite...

Page 7: ...espectively Selecting a Probe Input Press release the PGM button until one of the PROBE indicators begins to blink Use the UP or DOWN button to select the desired probe Relay Activity Relay activity for each ZONE is visible via front panel RELAY indicators When ZONE1 output is engaged the RELAY 1 indicator will illuminate When ZONE2 output is engaged the RELAY 2 indicator will illuminate Note All ...

Reviews: