This addendum describes how to enable and use the 2-stage 
cooling mode features available with TC-1 firmware version 

3.93 and higher. 

2-Stage Cool Mode

Basic Description: 

In 2-Stage cooling (C2) mode the TC-1 uses a single 

temperature probe to monitor glycol temperature 
and, based on stage 1 and stage 2 set points, 

engages stage 1 and stage 2 relays whenever glycol 
temperature is above each stage's respective set 

point.

C2 mode is only available while the Extended 

Function parameter (EF, accessible under the CC 
menu) is enabled. 

During programming, C2 mode is indicated by the 
illumination of both the COOL and AUTO front panel 

LEDs and by the characters “C2” displayed in the 
temperature window. During operating mode, the 

COOL and AUTO LEDs illuminate while glycol 
temperature is displayed in the Temperature window.

In multiple temperature probe applications, the 
controlling temperature probe is designated by the CP 

parameter (see TC-1 User's Guide).

Each stage's set point (SP1 and SP2) can be adjusted 

individually or ramped up and down together while 
maintaining their relative offsets.

Acrolon 

Technical Support

Phone:  707-938-1300 (option 2)
E-mail:

[email protected]

Web:

www.acrolon.com

Summary of Contents for TC-1

Page 1: ...TC 1 Controller USER S GUIDE ADDENDUM 2 Stage Cool Mode Firmware Version 3 93 ...

Page 2: ...r EF accessible under the CC menu is enabled During programming C2 mode is indicated by the illumination of both the COOL and AUTO front panel LEDs and by the characters C2 displayed in the temperature window During operating mode the COOL and AUTO LEDs illuminate while glycol temperature is displayed in the Temperature window In multiple temperature probe applications the controlling temperature ...

Page 3: ... If using two probes be sure to attach the probes in a bus topology e g from controller to TP 1 and then from TP 1 to TP 2 Make all cable splices as close to the probes as possible and use only moisture proof gel filled IDC connectors for splices Ensure that shield is contiguous from controller through to TP 2 Wire RELAY 1 to the solenoid or valve that controls STAGE 1 of the chiller Wire RELAY 2 ...

Page 4: ... Press the PGM button to advance to dCH dual zone cool heat and turn this setting On via the UP or DOWN button ...

Page 5: ...dvance to MODE selection as indicated by a blinking MODE light or the word OFF blinking in the SETPOINT window Prese the UP or DOWN button to select the desired thermostat MODE either COOL or HEAT Notes Only COOL and HEAT modes are affected when dCH is set to On Also the following parameters are ignored by the thermostat when dCH is set to On CP HP and Hr Please see TC 1 User s Guide for more info...

Page 6: ...ed in the TEMPERATURE display window Press the UP DOWN buttons to adjust SP2 to the desired value as shown in the SETPOINT display window Adjusting SP1 and SP2 Simultaneously Press and hold the PGM button While holding the PGM button depressed use the UP and DOWN buttons to adjust SP1 to the desired value as indicated in the SETPOINT window The value of SP2 also changes by this same amount despite...

Page 7: ...espectively Selecting a Probe Input Press release the PGM button until one of the PROBE indicators begins to blink Use the UP or DOWN button to select the desired probe Relay Activity Relay activity for each ZONE is visible via front panel RELAY indicators When ZONE1 output is engaged the RELAY 1 indicator will illuminate When ZONE2 output is engaged the RELAY 2 indicator will illuminate Note All ...

Reviews: