54
6.3.2
Secondary Injection Current Output
Unit
Ammeter
range
Accuracy
Trip current
CU-Ps
10.00A
±0.5%rdg±5d
10.5A
20.00A
±0.5%rdg±5d
21A
100.0A
±0.5%rdg±5d
105A
6.3.3
Auxiliary Metering Input
Auxiliary metering range
Full scale
Accuracy
300.0V RMS
300.0V
±0.7%rdg±5d
5.000A RMS
5.000A
±0.7%rdg±5d
6.3.4
Timing System
Timer mode
Range
Resolution
Accuracy
Internal start
0-999.999s/
9999.99s/
99999.9s
1ms/
10ms/
100ms
0.01% rdg
2d
Single contact
0-999.999s/
9999.99s/
99999.9s
1ms/
10ms/
100ms
0.01% rdg
2d
Dual contact
0-999.999s/
9999.99s/
99999.9s
1ms/
10ms/
100ms
0.01% rdg
2d
Current operated
0-999.999s/
9999.99s/
99999.9s
1ms/
10ms/
100ms
0.01% rdg
4d
Pulse
0-999.999s/
9999.99s/
99999.9s
1ms/
10ms/
100ms
0.01% rdg
2d