37
29
OPERATING STATES, cont.:
DISABLE FUNCTION
•
Press and hold red reset button for 1 second at any time to disable the burner
•
When you release the reset button the burner will return to normal operation
•
Genisys control has limited reset
•
Initial lockouts result in “soft” lockout.
Red light flashing—click the red reset button to restart
Recurring lockouts without completing a heat cycle will result in Restricted (“hard”) lockout.
Red light on steady—hold the red reset button 15 seconds until the yellow light turns on. You can
NOT reset the control by interrupting line voltage.
PUMP PRIME MODE
•
Prepare the burner for priming
•
Initiate a call for heat
•
After the burner starts, press and hold the reset button until the yellow light turns on. (15 seconds)
•
Release the reset button. The yellow light will turn off and the burner will start again
•
At burner start up, click the reset button
•
Enters 4-minute dedicated pump prime mode, with motor and igniter on, and oil valve energized.
The yellow light is on when in the pump prime mode
•
Terminate the call for heat and the control will exit the pump prime mode and resume normal
operation