BECKETT BURNER GENISYS™ CONTROL
Basic Features:
Three indicator lights:
•
Red reset button/lockout light
•
Pump Prime
•
Green flame/recycle light
Limited Reset
•
Recurring lockouts without a complete heat cycle puts control in restricted (hard lockout) mode
Limited Recycle
•
If flame is established and then lost, the control will recycle until the cumulative time trial for
ignition budget is exhausted and will then go into hard lockout. This prevents excessive oil
accumulation in the appliance
Valve on delay—15 seconds
Motor-off delay—none
Sequence of Operation
1. Standby 2. Valve-on delay 3. Trial for ignition 4. Lockout
5. Ignition carryover 6.
Run 7. Recycle
8. Motor-off delay 9. Pump prime
OPERATING STATES:
STANDBY
•
The burner is idle, waiting for a call for heat. When a call for heat is initiated, there is a ½ second
delay while the control performs a safe start check
VALVE-ON DELAY (pre-time)
•
The igniter and motor are on while the fuel solenoid valve remains de-energized—typically 15
seconds. Allows the burner to establish air flow and brings the pump to full speed, helping to keep
ignitions smooth and clean
TRIAL FOR IGNITION
The oil solenoid valve is energized. A flame should be established within the factory set trial for
ignition time (also known as “lockout time”) 15 seconds on the Genisys control