The upper level of the foundation casing must be 1-2 cm higher than the walking level in order to limit the
amount of rain water that can get inside.
Pour A-class concrete all around the casing up to approx 5-10 cm below the walking level. Wait all the time
required for the concrete to set firmly (at least 7 days) and then finish the surface work.
It is most important that the casing be1-2 cm higher than the area finished level. In no way Talos C730 is to
become a water gathering basin.
Avoid areas where soil tends to sag to prevent the bollard from staying flooded. In case of snow, the flat
surface of the cover plate can be easily cleared even by heavy machanical means.
Pic. 12
~ 1,1 m
~ 1,4 m
!
!
!
!
!
!
The bollard must be positioned and perfectly levelled
before concrete is poured all around the foundation cage.
Iron armature:
class B450C (ASTM A615 Grade 60) made of rebars whose yield
point is ≥ 450 MPa and breaking point ≥ 540 MPa.
Concrete specifications:
A- Class C25/30, aggregate type 10-30
and Rck ≥ 30 N/mm² in compliance with UNI EN 12620.
Concrete volume:
1,3
m³
Soil:
compaction index 90%, as per "Proctor" Test optimal curve,
in compliance with UNI EN 13286-2:2005.
Concrete:
to set for at least 7 days before the installation of the
bollard can be carried on.
~ 1,4 m
~ 1 m
1-2 cm
7,5 cm
Ø 50 mm
0.0
Soakaway
pebbles
Concrete
Asphalt
~ 1,1 m
a submersed
pump may be
needed
!