TM5-4120-375-14
THERMAL EXPANSION VALVE (CONT.)
LOCATION/ITEM
ACTION
REMARKS
INSTALLATION
5.
Thermal Expansion Valve
g.
h.
Position bulb in same
i.
j .
k.
Secure sensing bulb to suction line with two band
clamps (5).
Wrap the sensing bulb (6) with insulating tape
(Item 6, table D-1) being careful to avoid kinking
tube.
NOTE
position as it was removed.
Carefully install the sensing bulb to its position
on the suction line.
Clamp into position on the
suction line.
Cover suction line, sensing bulb and
clamps with insulating material.
Carefully form the capillary tube along adjacent
piping.
Leak check, evacuate and charge system in
accordance with paragraphs 5-16 thru 5-18.
5-58
Summary of Contents for UAC40-5/6-08
Page 2: ......
Page 4: ......
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 20: ......
Page 30: ......
Page 34: ......
Page 61: ...table D 1 table D 1 table D 1 table D 1 TM5 4120 375 14 4 27...
Page 77: ...TM5 4120 375 14 4 43 4 17...
Page 79: ...4 45 TM5 4120 375 14 4 18...
Page 81: ...TM5 4120 375 14 4 47 4 19...
Page 89: ...TM5 4120 375 14 a b c d e 4 55...
Page 91: ...TM5 4120 375 14 Change 1 4 5 7...
Page 137: ...4 103 TM5 4120 375 14...
Page 199: ...5 31 TM5 4120 375 14 table D 1...
Page 253: ...TM5 4120 375 14 5 85...
Page 285: ...TM5 4120 375 14 5 117...
Page 308: ......
Page 312: ......
Page 314: ...PIN 054090 001...
Page 324: ......
Page 331: ...TM 5 4120 375 14 Change3 E 3...
Page 332: ...TM 5 4120 375 14 Pin 0 5 4 0 9 0 0 0 3 E 4 U S GOVERNMENT PRINTING OFFICE 1995 655 121 20084...
Page 334: ......
Page 340: ......
Page 342: ......
Page 343: ......
Page 344: ......
Page 345: ......
Page 346: ......
Page 347: ......
Page 348: ......
Page 349: ......
Page 350: ......
Page 351: ......
Page 352: ......