WIRING
FUNCTION
TAMPER
VACANT L/C
1
2
3
4
5
6
7
8
POWER
ALARM
Power
}
Signal Input
Sensor
(N.C.)
Sensor
(N.C.)
■MODE SELECTOR
Switch
1
ON
OFF
(
Factory set
)
ALARM LED
The alarm LED will light up, synchronized with the
alarm contact, if you set the mode selector at ON.
Switch3
ON
N.O.
OFF
N.C.
(Factory set)
ON
:
N.O.
OFF
:
N.C.
ALARM CONTACT CHANGEOVER
Change alarm contact to N.O. when sensor is used for
an application other than security purpose, such as
light control.
SETTING OF SENSITIVITY
ON
OFF
120
%
100
%
(
Factory set
)
80
%
60
%
Switch
4・5
When operation check resultin excessive or insufficent high sensitivity of sensor,
change setting of sensitivity
with mode selector and
re-check operation.
Four settings are available.
ON
:
LONG
OFF
:
WIDE
Switch6
ON
LONG
OFF
WIDE
(Factory set)
PROTECTION PATTERN CHANGEOVER
Two protection patterns (Wide angle/Long range) are selectable by replacing lens.
Reselect the dip switch when exchanging lens (refer
to “3. DETECTION AREA”). Do not set the switch
OFF for long range protection.
FACTORY SET
ON
OFF
1 2 3 4 5 6
■Terminal Arrangement
■Basic connection
■WIRING DISTANCE BETWEEN SENSOR AND POWER SOURCE
When this setting is "ON", memory is always stored
when sensor is armed.
When an alarm has been activated, the memory LED
flashes for 3 min. and then remains lit for 47 min.
It automatically reset and memory is also canceled.
ALARM MEMORY CHANGEOVER
Memory LED will inform you which sensor initiated an alarm during alert conditions when
two or more sensors are connected on the same line.
ON
(
Factory set
)
Switch
2
OFF
NOTE : Same LED is used to indicate alarm and alarm memory.
POWER
(non-polarity)
9.5V to 28V DC
25mA Max.
Distance at 12VDC
Distance at 24VDC
Size of wire used
2500ft ( 750m)
14000ft ( 4400m)
4600ft (1400m)
28000ft ( 8500m)
AWG 22 (Dia.0.65mm)
AWG 18 (Dia.1.0mm)
AWG 16 (Dia.1.25mm)
8500ft (2600m)
50000ft (15200m)
[When two units are used]
Note : 1)
2)
*
Allow approx. one minute for warm-up after power is supplied.
(Alarm LED is flashing) In the meantime, no alarm is initiated.
*
After the one minute has passed, the unit will be in the armed
condition and will trigger an alarm when detecting a human
body.
Maximum wiring distance, when two or more sets are connected, is
the value above divided by numbers of sets.
The signal line can be wired to a distance of 3,280 ft (1,000m) with
AWG 22 (0.65mm dia.) wire.
Sensor operation can be adjusted to fit the environmentals / applications with the built-in mode selector.
ALARM OUTPUT
Dry contact (semi-conductor)
N.C./N.O. selectable
Reset : approx. 2 sec.
30V DC (24V AC) 0.25A Max.
(Protective resistor 3.3Ω)
VACANT
LED Control
(Refer to section “6.FUNCTION”)
TAMPER OUTPUT
Dry contact N.C.
Operation : Open when cover is detached.
30V DC 0.1A Max.
LED CONTROL
LED can be remotely controlled from the control panel. Even after setting
alarm LED OFF, combined use of alarm LED control terminal (6 LED
Control) and power terminal (negative) enables to reset the mode back to
alarm LED ON, which makes it easy to operate a walk test even after
installation of the sensor.
Alarm LED is lit by switching ON
CONTROLLER
POWER
SENSOR 1
SENSOR 2
Set alarm LED OFF
OPERATION CHECK
NOTE :
2 : Low voltage
TROUBLE ALARM
NOTE :
1 : Unit trouble
This function checks / monitors sensor unit itself in accordance with built-in
program.
When trouble is found out as a result of the check / monitor, alarm LED lights
and an alarm signal also continuously outputs.
Trouble alarm outputs when inner circuit / wiring is damaged / broken.
See "8. TROUBLESHOOTING" and remedy table.
The monitor functions regardless of mode settings but an alarm is
not indicated in case of setting alarm LED at OFF position.
When power is reset during the alarm status, trouble alarm stops
only for warming up time.
When power voltage of sensor drops down (approx. 8.5V DC or less),
trouble alarm outputs before sensor operation becomes unstable due to low
voltage. See "8. TROUBLESHOOTING" .
The monitor functions regardless of mode settings but an alarm is
not indicated in case of setting alarm LED at OFF position.
When power voltage recovers to normal level during the alarm
status, trouble alarm stops.
When installation is completed, turn the power "ON" and check operation after about 1min. warming up time, as follows:
1. Make sure that alarm LED finished flickering.
2. Make a walk test in the protected area to check if an alarm is initiated.
Check alarm LED and control panel for sensor operation.
3. After correct operation has been confirmed, use the mode selector
switch to disable the alarm LED, if required.