background image

1. Terminal Configuration

2. Wiring distance

SUPPLY VOLTAGE

12V to 30VDC (Non Polarity)

Power consumption 
35mA MAX (MS-12TE)
40mA MAX (MS-12FE)

OUTPUT SIGNAL

Dry contact relay output form N.O/N.C selectable

CONTACT OPERATON

Detection time + off delay (2sec.-5min. approx.)

CONTACT CAPACITY

30V (AC/DC), 0.5A MAX. (resistive load)

DAY LIGHT

Output operates when daylight is below setting.

TAMPER

Dry contact relay output N/C

CONTACT CAPACITY

30V (AC/DC), 0.5A MAX. (resistive load)

WIRE SIZE

AWG24 ~ AWG14 (0.2mm

2

) ~ (2mm

2

)

Exposed wiring

Mounted wiring

Power voltage

DC12V

DC24V

0.3mm

2

(ø0.65mm)

820’ (250m)

8,500’ (2600m)

0.5mm

2

(ø0.8mm)

1,480’ (450m)

14,100’ (4300m)

0.8mm

2

(ø1.0mm)

2,300’ (700m)

21,300’ (6500m)

1.2mm

2

(ø1.25mm)

3,120’ (950m)

29,500’ (9000m)

Note: 1) Maximum wiring distance when two or more sets are 

connected is the value above divided by number of sets.
2) The signal line can be wired to a distance of up to 3,000ft. 
(1,000m) with AWG 22 (dia. 0.65mm) telephone wire.

3. Wire Insertion

Break one outside knockout and its related inside knockout 
as necessary.
Pull wire through the insertion holes and connect it to the 
terminals.

Break inside knockout, 
pull wire through wiring 
hole and connect it to the 
terminals.

* When installing the sensor 

to flush mount box, use 
wall mount bracket (BW-
24) [sold separately].

Outside

knockout

Inside
knockout

Wiring
hole

Wiring
box

Outside
knockout

(1) Read PRECAUTIONS (3) before installation.
(2) Loosen cover locking screw and detach cover.

(3) Refer to WIRING (6) and connect wires to the terminal.
(4) Install the unit.

(5) Refer to DETECTION 

AREA (4) and OPERATION 
CHECK (8) and check 
detection area and operation.

(6) Replace the cover.

Power

Cover locking screw

Contact output

Tamper

Size of wire

Summary of Contents for MS-12TE

Page 1: ... human body Suitable for indoor outdoor 1 This sensor is equipped with an AND detection and pulse count system 2 The AND detection system will issue an alarm signal only when detection occurs in both horizontal and downward zones simultaneously 3 The sensor is equipped with many features such as Alarm output control depending on the illuminance of the surrounding area Á Output time delay switch se...

Page 2: ...esn t output signal This sensor operates during detecting time delay time set by a potentiometer It continues to issue alarm as long as it detects objects regardless of set delay time Do not pour water on this unit with a hose as it is designed to be rainproof not waterproof When detection mode is set at AND mode this sensor outputs alarm signal only when both upper and lower sensor detect objects...

Page 3: ...OP VIEW Wall Detection DETECTION MODE OR Fine Adjustment 3 3 3 3 Masking unnecessary zones Variable range Downward zone 10m 33 10m 33 5m 16 5 5m 16 5 0 Detection distance is set by adjusting the angle of downward zone Adjusting range 10 3m to 40 12m 7 ranges Detection distance is set by adjusting the angle of downward zone Adjusting range 10 3m to 40 12m 7 ranges The detection zone of this unit co...

Page 4: ...ment Detection distance can be adjusted within a range from 10 3m to 40 12m by turning the angle of downward zone vertically Refer to the index and slide the adjustment lever up or down Slide it up and the detection distance becomes shorter sliding it down detection distance becomes longer Detection distance depends on how the sensor is installed and how its sensitivity adjustment is set Area mask...

Page 5: ...e can be adjusted between 2sec and to 5min approx Delay time ON OFF ON OFF Factory set ON 1a 1b OFF a N O b N C Factory set Less sensitive prevents false alarms caused by temperature fluctuation More sensitive ON OFF ON OFF Factory set Lights at alarm LED disabled During warm up period light flickers ON OFF AND OR Factory set Alarm signal is issued only when both upper and lower sensors detect obj...

Page 6: ... when two or more sets are connected is the value above divided by number of sets 2 The signal line can be wired to a distance of up to 3 000ft 1 000m with AWG 22 dia 0 65mm telephone wire 3 Wire Insertion Break one outside knockout and its related inside knockout as necessary Pull wire through the insertion holes and connect it to the terminals Break inside knockout pull wire through wiring hole ...

Page 7: ...stment 1 Readjust the protection area setting 2 Improper operation mode setting 2 Readjust operation mode setting 3 Cover face is soiled with dust or water drop 3 Clean the cover with soft cloth 4 Area covered by both upper and lower sensor is too small to be 4 Readjust the sensor angle detected when set at AND mode Only applicable to MS 12FE Activated when no 1 Unstable power voltage 1 Stabilize ...

Page 8: ... to 122ºF 20ºC to 50ºC Mounting position Indoor Outdoor Height 0 8 1 2m Weight 13 7oz 390g 16 5oz 470g Appearance Body AES resin Lens PE resin Accessory Tapping screw 2 Tapping screw 2 Area masking sheet 1 Area masking sheet 2 Optional Wall mount attachment BW 24 Pole attachment BP 22 TAKEX Europe Limited Aviary Court Wade Road Basingstoke HANTS RG24 8PE UK Tel 44 0 1256 475555 Fax 44 0 1256 46626...