background image

When the sensor is soiled, clean the cover with a soft cloth moistened with a small amount of cleaning solution.

Check operation once a week.

Do not fail to check oparation whenever a furniture in the place is moved.

When low battery alarm sounds, change battery for new one immediately.

If it is left, it could cause inactiveness of the sensor.

 Maintenance

1. Turn power on, and confirm power on notice 

sounds.

(In  case  of  battery  use,  confirm  power  on   

notice when connecting the battery.)

2. Ignite a lighter etc. within detection area for 

more than the set time.

3.  After  the  set  time,  buzzer  sounds  intermittently 

and LED flashes. (Alarm action)

4.  10sec.  after  the  flame  goes  off,  the  above 

alarm action ends.

Do  not  use  a  lighter  in  no  fire 

zone because it is dangerous.

In  such  case,  operation  test 

have to be done in other place 

with sensor only.

Detection  area  spreads  out  in 

front  of  the  sensor  at  approx. 

120

°

conically.

The  size  of  the  detection  area 

is  in  proportion  to  the  size  of 

the flame.

The  size  of  the  detection  area 

increases  with  an  increase  in 

flame size and duration.

When  the  object  of  detection  is  from  a  source  such  as  a  lighter, 

confirm detection throughout the area.
Use the optional BCW-401 universal bracket when area adjustment 

is required.

Approx. 120°

10' (3m)

10' (3m)

20' (6m)

20' (6m)

30' (9m)

30' (9m)

33' (10m)

33' (10m)

7

DETECTION AREA

9

TROUBLESHOOTING

8

OPERATION CHECK

20'

(6m)

20'

(6m)

10'

(3m)

10'

(3m)

10'

(3m)

10'

(3m)

16'

(5m)

16'

(5m)

Solve possible problems according to the following table .

If normal operations can not be restored by these corrective actios, contact either 

the dealer from whom you bought the unit or TAKEX.

Trouble  

Completely inactive 

Sometimes inactive 

Activated without 

flame 

The alarm LED 

flashes and buzzer  

sounds (5sec./once)

The alarm LED and    

buzzer works but the 

connected devices are

inactive (when wired)

The alarm LED        

lights on but buzzer

does not sound

Check 

No battery connected 

Low battery

No power supply (Broken wire or improper wire) 

Low voltage (When power supply wired)

Sensor inside is wet by condensation etc. 

Interrupting rays objects in front of detection area 

  (Glass, transparent resin are interrupting rays objects)

Improper area setting

Low voltage 

Low battery

Detection window is soiled with dust

Large electrical noise source such as a redio station or     

  high-voltage wire nearby

Unexpected ultraviolet rays nearby (Ref : 2, ATTENTION)

Sensor inside is wet by condensation etc.

Low battery     

  (Low battery alarm)

Buzzer "OFF"  

Poor contact output connection or broken wire 

The connected unit's trouble                        

Relocate the sensor to appropriate position

Use a BCW-401 (optional) and adjust the 

  angle setting

Remove tha dust and soil

Correct power supply

Change battery

Relocate the sensor

Remove the origin of the ultraviolet rays, 

   interrupt ultraviolet rays, or relocate the sensor

Dry out sensor inside, and remove the cause of wet

Change battery immediately

Buzzer "ON"

Check the wiring or connection

Check the connected unit

Connect battery

Change battery

Correct power supply or replace broken 

   wire

Dry out sensor inside, and remove the 

   cause of the wet

Remove the interrupting rays object

 Corrective action

  Side view : Ceiling / wall mount

 Front view : Ceiling mount

 Top view   : Wall mount 

When external output is used by wiring, 

a continuous output is issued during the 

above 3. and 4. alarm action.

Confirm the operation of the connected 

devices.

Detection area

Factory default setting

Detection timer : 1 sec.

Detection sensitivity : H (100%)

Detection object : Gas flame of lighter [2.75" (7cm)]

     

1)

2)

3)