12-6. T-K3 ON/OFF conditions: Overview
The T-K3 has tw o modes of ON/OFF conditions.
Select either mode by changing Dipsw itch 3 on the
upper bank of dipsw itches as shown in the picture
to the right.
Intermittent mode
This mode is the nor mal, default mode.
Continuous mode
This mode is for heating systems that deal w ith
smaller temperature differentials.
ON/OFF Conditions
Intermittent mode
(Default setting)
<Dipswitch set to OFF>
Continuous mode
<Dipswitch set to ON>
Conditions needed to
turn the T-K3 ON.
The BTU requirement is more
than 14,880 BTU/h
AND
The w ater flow rate is more
than 0.52 GPM
The BTU requirement is more
than 11,900 BTU/h
AND
The w ater flow rate is more
than 0.52 GPM
Conditions needed to
turn the T-K3 OFF
The BTU requirement is less
than 11,900 BTU/h
OR
Inlet temperature is higher
than the set temperature
OR
Outlet temperature is over
194°F
OR
The w ater flow rate is less
than 0.4 GPM
The BTU requirement is less
than 7,440 BTU/h
OR
Inlet temperature is higher
than the set temperature
OR
Outlet
temperature is over
194°F
OR
The w ater flow rate is less
than 0.4 GPM